12.4.2. Parameters 

[2..5 / 5] PID settings 

and ECM

The Proportional-Integral-
Derivative controller (PID 
controller) calculates a 
difference between measured 
values and set points. The 
PID controller minimizes the 
difference between those 
values by adjusting openness 
of the valves, damper 
actuator or fan speed. Adjust 
PID gains according to each 
project’s specifications. The 
default values may not be 
suitable for all applications. 

Tuning a PID controller 
involves setting values of 
Proportional gain (Kp), 
Integral gain (Ki) or Derivative 
gain (Kd) parameter values. 
If two-term (PI) or one-term 
(P) control is needed adjust 
unnecessary values to zero.

The C35-VAV… uses 6 PID 
controls. The PID controller 
parameters can be adjusted 
for the following functions:

VAV temperature [2/5]

VAV Air quality [3/5]

Valve [3/5]

Dehumidification [4/5]

Fan Temperature [4/5]

Fan Air Quality [5/5]

Adjustments can be made 
using the +/- buttons. Once 
the required adjustments 
have been made, select        
on each screen to save your 
changes.

The analog output signal for the EC motor can be configured with three parameters:

“ECM Min Off voltage”

: If this value is different from zero volts, adjust the ECM OFF voltage

to value that will turn off the ECM fan. 

“ECM MIN voltage”

: Defines the minimum signal value and the minimum speed of the fan

(5 %). 

“ECM MAX voltage”

: Defines the maximum signal value and the maximum speed of the

fan (100 %). 

Adjustments can be made using the +/- buttons. Once the required adjustments have been 
made, select        to save your changes. 

The C35-VAV… can be 
calibrated by adjusting the 
offset values on the device. 
Adjust offset values for 
each sensor using the +/- 
buttons. 

Select        to save 
your changes. Once the        
button has been pressed, the 
temperature will be updated 
to reflect the input of the 
offset value.

12.5. Offsets 

NOTE

: Ensure all sensors have had sufficient time to power up and stabilize prior to entering 

offset values. For more information see, “First Power Up an Commissioning”

Setpoint limits are defined in 
the “SP limits” menu. Limits 
can be set for temperature, 
air quality, and relative 
humidity in heating and 
cooling control modes and 
for all operating modes. Once 
setpoint limits have been 
defined, users will not be able 
to adjust setpoints outside 
the defined limits. 

Adjust the limits for each 
setpoint on screens 1 to 4 
using the +/- buttons. 
Select        to save your 
changes.

Select the “Language” button 
on Advanced menu screen. 
Select the desired language 
from the available options 
and then press the “Save” 
button to save the changes.

12.6. Setpoint Limits

12.7. Language

Содержание C35-VAV...

Страница 1: ...C35 VAV Technical Manual Configurable zone temperature carbon dioxide and relative humidity controller for VAV systems and universal HVAC applications Firmware Version C35 VAV 1 0...

Страница 2: ...11 7 Sound On Off 11 8 About 12 Advanced Menu 12 1 Network 12 2 Security 12 3 Parameters 1 5 Main Configuration 12 4 Parameters 2 5 5 Air volume VAV Temperature PID and ECM 12 5 Offsets 12 6 Setpoint...

Страница 3: ...pied mode function Three operating modes Comfort Economy Standby Protection functionality in Standby mode Password protected menu and advanced menu Window contact or presence sensor input Automatic or...

Страница 4: ...ng conditions include inside facing walls which are in an open and central location of the unit s area of operation Warning In order to ensure accurate readings and correct operation the unit should n...

Страница 5: ...ll connections are in the correct terminals and that the correct voltage is being provided 3 Attach C35 VAV to the wall mount by sliding the unit onto the mounting brackets as shown in the diagrams be...

Страница 6: ...cedure is repeated on an ongoing weekly basis 7 Touch screen operation and Maintenance The C35 VAV is primarily operated through its 3 5 resistive touch screen The screen should not be operated with s...

Страница 7: ...ted or modified in the parameter screen a Save button will appear allowing users to save their changes If the Save button is not selected prior to changing screens any changes will not be saved and th...

Страница 8: ...an be adjusted in the setpoints menu 10 2 Economy mode 10 1 Comfort mode This mode prioritises user comfort and it is recommended that Comfort mode is activated only when the controlled zone is occupi...

Страница 9: ...mes The device will automatically manage the HVAC system to regulate temperature within the specific setpoints for each scheduled working mode Comfort Economy and Standby See page 17 for Scheduler set...

Страница 10: ...ase buttons on the home screen Once the required adjustments have been made select to save your changes 11 3 Setpoints Configuring Daily Scedules Once the week long schedule has been set the daily pro...

Страница 11: ...e to the total number of devices on the data bus Max Info Frames The maxium number of requests a device is able to send over the local network For optimal network performance this value should be set...

Страница 12: ...n operates only when Heating is active and according to the ambient temperature the lower the ambient temperature the higher the fan speed Parallel with heat exchanger VAV damper actuator will be cont...

Страница 13: ...FF voltage to value that will turn off the ECM fan ECM MIN voltage Defines the minimum signal value and the minimum speed of the fan 5 ECM MAX voltage Defines the maximum signal value and the maximum...

Страница 14: ...een closed the system will resume normal operation If the Presence sensor parameter is selected and presence sensor is not detecting any presence the system will go from Comfortable mode to Economy mo...

Страница 15: ...0 V T1 Floor temperature sensor Pt1000 Q1 Remote air quality sensor 0 10 V 0 2000ppm Main configuration Control sequence Heating only Cooling and heating Cooling heating coil Enabled Fan operating mod...

Страница 16: ...lve actuator DC 0 10V cooling S1 Switch for window contact or presence sensor C1 BACnet MS TP bus connection C35 VAV with VAV damper actuator heating or cooling coil and ECM fan D1 Zone controller C35...

Страница 17: ...ow Maintain same polarity between devices on a single power supply 17 3 Maximum number of devices on data bus The C35 VAV B RS is categorized as BACnet MS TP Master device The maximum number of Master...

Страница 18: ...0 ppm 3 of measured value Step response time 90 3 minutes Sampling intervals 5 seconds Warming up time 3 minutes Calibration time 7 Days Display Type Graphical TFT LCD Touchscreen type Resistive singl...

Страница 19: ...ce instrument Codis has not had enough time to power up and stabilize Read chapter First start up and Commissioning Relative humidity reading is incorrect The device has not been calibrated Calculate...

Страница 20: ...ssary The device does not communicate over the BACnet MS TP network Count the number of devices on the network segment The maximum number of devices on a network segment has been exceeded Install a BA...

Страница 21: ...ER Product Name C35 VAV Product Model Number C35 VAV B RS G Application Software Version unknown Firmware Revision unknown BACnet Protocol Revision 14 Product Description C35 VAV is a configurable zon...

Страница 22: ...Point To Point modem Clause 10 baud rate s LonTalk Clause 11 medium __________ BACnet ZigBee ANNEX O Other Device Address Binding Is static device binding supported This is currently necessary for tw...

Страница 23: ......

Отзывы: