40
C35-VAV
41
C35-VAV
21. Factory reset
Caution: All stored data will be deleted. This should only be used in situations where all
parameters need to be reset to their default values.
The C35-VAV has factory default function built into the boot menu. To perform a factory
reset:
1. Reset the device by following procedure described in chapter Device reset
2. When the device enters the boot menu, touch and hold the screen when it boot
status reaches the “Press to reset all parameters” section.
3. The device will boot up with all the default parameters.
NOTE
: As the device has been reset to factory settings, please follow the first boot up and
commissioning instructions (page 10).
22. Calibration of resistive touchscreen
The resistive touchscreen has been calibrated during the production process. In the
unlikely event the touchscreen needs to be recalibrated please follow these steps:
•
Reset the device by following procedure described in chapter Device reset
•
When the device enters the boot menu, touch and hold the screen when it boot
status reaches the “Touch screen (press to calibrate)…”
•
Press and hold the screen until the calibration procedure begins
Follow the instructions on the screen.
23. BACnet Protocol Implementation Conformance Statement
BACnet Protocol Implementation Conformance Statement
- PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT (NORMATIVE)
(This annex is part of this Standard and is required for its use.)
BACnet Protocol Implementation Conformance Statement
Date: May 2, 2014
Vendor Name: KOER
Product Name: C35-VAV...
Product Model Number: C35-VAV-…-B/RS(-G)
Application Software Version: unknown
Firmware Revision: unknown BACnet Protocol Revision: 14
Product Description:
C35-VAV is a configurable zone temperature and air quality controller for pressure
depended or pressure independent VAV systems.
BACnet Standardized Device Profile (Annex L):
BACnet Operator Workstation (B-OWS)
BACnet Advanced Operator Workstation (B-AWS)
BACnet Operator Display (B-OD)
BACnet Building Controller (B-BC)
BACnet Advanced Application Controller (B-AAC)
BACnet Application Specific Controller (B-ASC)
BACnet Smart Sensor (B-SS)
BACnet Smart Actuator (B-SA)
ANNEX A
BACnet Protocol Implementation Conformance Statement
List all BACnet Interoperability Building Blocks Supported (Annex K):
BIBB
Service
DS-RP-B
Data Sharing - Read Property-B
DS-RPM-B
Data Sharing - Read Property Multiple-B
DS-WP-B
Data Sharing - Write Property-B
DM-DDB-B
Dynamic Device Binding
DM-DOB-B
Dynamic Object Binding
Segmentation Capability:
Able to transmit segmented messages Window Size _____
Able to receive segmented messages Window Size _____
Standard Object Types Supported:
An object type is supported if it may be present in the device. For each standard Object
Type supported provides the following data:
1. Whether objects of this type are dynamically creatable using the Create Object
service
2. Whether objects of this type are dynamically deletable using the Delete Object
service
3. List of the optional properties supported
4. List of all properties that are writable where not otherwise required by this standard
5. List of proprietary properties and for each its property identifier, data type, and
meaning
6. List of any property range restrictions