The AI1 analog input 
parameter allows the 
following sensors to be 
connected and enabled 
in In/Out menu:

VAV actuator position
signal

Remote CO

2

 sensor

Disabled (default)

Select        to save your 
changes.

13. Input/Output Menu

13.1. Analog input (AI1)

The remote sensor can be activated by selecting “Remote sensor” from the available ‘Sensor 
function’ parameter options. Once selected, the Remote sensor parameter will appear. Select 
      to save your changes.

The Floor heating sensor function requires floor temperature sensor to be connected and 
enabled in settings. Enable floor sensor by selecting Floor sensor from the available “Sensor 
function” parameter options. Select        to save your changes.

Max Floor Temperature: If the floor sensor parameter is enabled, a “Max floor temperature” 
parameter will appear at the bottom of In/Out screen 1/2. Adjust maximum floor temperature 
by using the +/- buttons. Select        to save your changes.

13.4. Temperature sensor

Users can define how temperature readings will be displayed by pressing the button next to 
“Temperature Sensor“. The options are:

Internal

: The temperature as measured by the device’s inbuilt sensor.

Remote

: If a remote sensor is connected, the temperature as measured by the remote

sensor.

Min, Max, Average

: If a remote sensor is connected, the measured temperature can be a

calculated using minimum, maximum or average reading of the two sensors.

Select        to save your changes.

13.3.3. Floor sensor

13.2. Binary input (BIN1)

If a window contact swich or presence sensor is connected to binary input (BIN1) change Binary 
input parameter from “Disabled” to “Window contact” or “Presence sensor”.
If the “Window contact” parameter is selected and window’s contact switch is triggered by an 
open window, then the system will go into standby mode to save energy. The operating status 
on the home screen will state “Standby - Window is Open” to notify users. Once the window 
has been closed, the system will resume normal operation.
If the “Presence sensor” parameter is selected and presence sensor is not detecting any 
presence the system will go from “Comfortable mode” to “Economy mode”. The operating status 
on home screen will state “Economy mode – No presence detected”. Once the presence is 
detected the system will resume to “Comfortable mode”.

The contact polarity can be reversed by selecting the Binary input polarity “Normally open” or 
“Normally closed”. 

Select        to save your changes.

13.3. Sensor Function

The analog RTD sensor (PT1000) parameter has the following available options if the sensor is 
connected to the device’s RTD input:

Disabled (Default value, an external sensor is connected but has not been enabled)

Changeover sensor

Remote sensor (Temperature only)

Floor sensor

If a sensor is not connected or a sensor with different resistance to that of a PT1000 is 
connected, a message “Not connected” will be shown instead.

A changeover sensor allows the system to automatically switch between heating and cooling 
mode (or vice versa) using the “Sensor function” parameter on Screen 1/2 of the Input / Output 
menu. If the sensor function parameter is set to “Changeover”, the device will automatically 
change from heating or cooling as required. Changeover will be determined by the temperature 
in the duct or pipe. If the temperature in the duct or pipe is above 28°C the control mode will 
change to heating or if the temperature is below 18°C the control mode will be changed to 
cooling. Select        to save your changes.

13.3.1. Change Over

13.3.2. Remote sensor

13.5. Values

Screen [2 / 2] of the 
In/Out menu summarizes 
all of the values and states 
of the device’s inputs and 
outputs. These values are 
refreshed every second.

14.1. VAV systems without ECM fan

14. Variable Air Volume applications using C35-VAV

D

 - Damper actuator 0 - 10 V

T1

 - Remote temperature sensor Pt1000

Q1

 - Remote air quality sensor 0 – 10 V

Main configuration

Control sequence:   

Heating only 
Cooling only
Cooling or heating 
Ventilation

Cooling/heating coil:  

Disabled

Fan operating mode:  

Off

Dehumidification:    

Disabled

14.1.1. Single duct

Содержание C35-VAV...

Страница 1: ...C35 VAV Technical Manual Configurable zone temperature carbon dioxide and relative humidity controller for VAV systems and universal HVAC applications Firmware Version C35 VAV 1 0...

Страница 2: ...11 7 Sound On Off 11 8 About 12 Advanced Menu 12 1 Network 12 2 Security 12 3 Parameters 1 5 Main Configuration 12 4 Parameters 2 5 5 Air volume VAV Temperature PID and ECM 12 5 Offsets 12 6 Setpoint...

Страница 3: ...pied mode function Three operating modes Comfort Economy Standby Protection functionality in Standby mode Password protected menu and advanced menu Window contact or presence sensor input Automatic or...

Страница 4: ...ng conditions include inside facing walls which are in an open and central location of the unit s area of operation Warning In order to ensure accurate readings and correct operation the unit should n...

Страница 5: ...ll connections are in the correct terminals and that the correct voltage is being provided 3 Attach C35 VAV to the wall mount by sliding the unit onto the mounting brackets as shown in the diagrams be...

Страница 6: ...cedure is repeated on an ongoing weekly basis 7 Touch screen operation and Maintenance The C35 VAV is primarily operated through its 3 5 resistive touch screen The screen should not be operated with s...

Страница 7: ...ted or modified in the parameter screen a Save button will appear allowing users to save their changes If the Save button is not selected prior to changing screens any changes will not be saved and th...

Страница 8: ...an be adjusted in the setpoints menu 10 2 Economy mode 10 1 Comfort mode This mode prioritises user comfort and it is recommended that Comfort mode is activated only when the controlled zone is occupi...

Страница 9: ...mes The device will automatically manage the HVAC system to regulate temperature within the specific setpoints for each scheduled working mode Comfort Economy and Standby See page 17 for Scheduler set...

Страница 10: ...ase buttons on the home screen Once the required adjustments have been made select to save your changes 11 3 Setpoints Configuring Daily Scedules Once the week long schedule has been set the daily pro...

Страница 11: ...e to the total number of devices on the data bus Max Info Frames The maxium number of requests a device is able to send over the local network For optimal network performance this value should be set...

Страница 12: ...n operates only when Heating is active and according to the ambient temperature the lower the ambient temperature the higher the fan speed Parallel with heat exchanger VAV damper actuator will be cont...

Страница 13: ...FF voltage to value that will turn off the ECM fan ECM MIN voltage Defines the minimum signal value and the minimum speed of the fan 5 ECM MAX voltage Defines the maximum signal value and the maximum...

Страница 14: ...een closed the system will resume normal operation If the Presence sensor parameter is selected and presence sensor is not detecting any presence the system will go from Comfortable mode to Economy mo...

Страница 15: ...0 V T1 Floor temperature sensor Pt1000 Q1 Remote air quality sensor 0 10 V 0 2000ppm Main configuration Control sequence Heating only Cooling and heating Cooling heating coil Enabled Fan operating mod...

Страница 16: ...lve actuator DC 0 10V cooling S1 Switch for window contact or presence sensor C1 BACnet MS TP bus connection C35 VAV with VAV damper actuator heating or cooling coil and ECM fan D1 Zone controller C35...

Страница 17: ...ow Maintain same polarity between devices on a single power supply 17 3 Maximum number of devices on data bus The C35 VAV B RS is categorized as BACnet MS TP Master device The maximum number of Master...

Страница 18: ...0 ppm 3 of measured value Step response time 90 3 minutes Sampling intervals 5 seconds Warming up time 3 minutes Calibration time 7 Days Display Type Graphical TFT LCD Touchscreen type Resistive singl...

Страница 19: ...ce instrument Codis has not had enough time to power up and stabilize Read chapter First start up and Commissioning Relative humidity reading is incorrect The device has not been calibrated Calculate...

Страница 20: ...ssary The device does not communicate over the BACnet MS TP network Count the number of devices on the network segment The maximum number of devices on a network segment has been exceeded Install a BA...

Страница 21: ...ER Product Name C35 VAV Product Model Number C35 VAV B RS G Application Software Version unknown Firmware Revision unknown BACnet Protocol Revision 14 Product Description C35 VAV is a configurable zon...

Страница 22: ...Point To Point modem Clause 10 baud rate s LonTalk Clause 11 medium __________ BACnet ZigBee ANNEX O Other Device Address Binding Is static device binding supported This is currently necessary for tw...

Страница 23: ......

Отзывы: