18
(40) Enter permanent code (-):
(41) Measurement operation (NO):
This activates measurement operation for chimney sweep
measurements.
IMPORTANT: The control of output is then not function-
ing: provide for sufficient thermal acceptance.
5.3.2 The F4 KEY: "PYROT Loader System"
(screen number) parameter (factory setting)
(01) Cleaning (NO):
This activates the cleaning function. Exhaust fan at start-
ing speed, and moving grate on.
(05) Moving grate, pause (60 s):
Cycle switching for the moving grate (adjustable pause
time, impulse fixed, 2 seconds).
(07) Metering container,empty running time (5s):
Running time for feed auger with the light barrier for the
feed auger clear
prompt for material
(08) Conveyor Device 1/Delay (3 s):
Delay before connecting Conveyor System 1
(e.g. rotary valve, conveyor auger, etc.)
(09) Conveyor System 1, after-running (0 s):
After-running of Conveyor System 1
(e.g. pneumatic conveyor, etc.)
(10-37) Conveyor Systems 2-15:
Delay before connecting or after-running of Conveyor Sys-
tems 2 to 15
(38) Extraction System 1/Delay (3 s):
Delay before connecting Conveyor System 1
(e.g. spring-operated extraction system, inclined extraction
system, etc.)
(39) Extraction System 1/Impulse (5 s):
Impulse for the cycle switching for Extraction System 1
(e.g. spring-operated extraction system, inclined extraction
system, etc.)
(40) Extraction System 1, Pause (0 s):
Pause in the cycle switching for Extraction System 1 (e.g.
spring-operated extraction system, inclined extraction sys-
tem, etc.)
(41) Extraction System 2/Delay (3 s):
Delay before connecting Conveyor System 2
(e.g. spring-operated extraction system, inclined extraction
system, etc.)
(42) Extraction System 2/Impulse (5 s):
Impulse for the cycle switching for Extraction System 2
(e.g. spring-operated extraction system, inclined extraction
system, etc.)
(43) Extraction System 2, Pause (0 s):
Pause in the cycle switching for Extraction System 2
(e.g. spring-operated extraction system, inclined extraction
system, etc.)
(44)Extraction System 1/Hydraulics/Delay
(5 s):
Delay before connecting hydraulic drive for Extrac-
tion System 1
(45) Extraction System 2/Hydraulics/Delay
(5 s):
Delay before connecting hydraulic drive for Extrac-
tion System 2
(50) Silo filling:
Start silo filling (only possible when the
facility is not in operation and has cooled off).