17
5.3 Boiler and loader system (F3/F4)
5.3.1 The F3 KEY: "PYROT Parameters"
(screen number) parameter (factory setting)
(01) Storage unit temperatures ( - ):
Indication of all the storage unit temperatures
(Indication only for storage unit option)
(02) Return flow, boiler (70°C):
Set point value for boiler backflow circuit valve
(03) Forward flow, boiler (80°C):
Set point value for boiler temperature
(04) Exhaust gas, boiler (200°C):
Limit of maximum exhaust gas temperature
(05) Exhaust gas, residual O2 (7%):
Set point value for residual oxygen for air vent control
(06) O2-control (ON):
If the lambda sensor is defective, the O2-control system
can be switched off (emergency operation).
(07) Air vents without O2-control system (100%):
Position of the air vents with O2-control switched off
(only with O2-control system switched off)
(08) Carry away excess heat at (95°C):
Limit temperature for carrying away excess heat
(10) Load storage unit with oil/gas operation to (storage
unit at bottom):
To which heat storage sensor should the storage unit be
loaded with oil/gas operation?
(Indication only with option of storage unit and oil/gas
burner on PYROT ECO)
(11) Load storage unit with oil/gas operation to (70°C):
To what temperature should the storage unit be heated up
with oil/gas operation?
(Indication only with option of storage unit and oil/gas
burner on PYROT ECO)
(12) System Temperature Set Point Minimum (50°C):
Minimum forward flow temperature for heat distribution
provided by customer (only if System Temperature Set
Point Minimum YES
Service Menu)
(14) Load storage unit to (STORAGE UNIT AT BOTTOM):
To which heat storage sensor should the storage unit be
loaded with wood operation?
(Indication only for storage unit option)
(15) Load storage unit to (80°C):
To what storage unit temperature should the storage unit
be heated up with wood operation?
(Indication only for storage unit option)
(16) Storage Unit Management, Temperature, Storage Unit
Average (80°C):
Set point value, average temperature, storage unit
boiler output is reduced according to loading of storage
unit. (Indication only for storage unit option)
(17) Start boiler when the system temperature is fallen
short of. Set point (accumulator sensor at bottom):
When the accumulator sensor falls short of the system set
point, the boiler will be heated up.
(Indication only for storage unit option)
(20) External release for boiler (NO):
Is the boiler to be switched on and off by an external
floating contact?
(Indication only with the option "Automatic Start, External
Prompt".)
(21) Material take-back larger with air vent positioning
(50%):
Material take-back by means of adjustable air vent posi-
tioning.
(23) Feed auger cycle heat-up (5%):
Insertion of material after ignition
(24) Feed auger, maximum (100%):
Maximum insertion of material
(25) Pneumatic boiler tube cleaning system (500 s):
Cleaning cycle for the pneumatic cleaning system
(28) Wood operation, load ( 0 ):
Operating hours/minutes, full load, PYROT
(30) Oil/Gas operation ( 0 ):
Operating hours/minutes, oil/gas operation, PYROT ECO
(31) Date/Year (current):
Set year
(32) Date/Month (current):
Set month
(33) Date/Day (current):
Set day
(34) Date/Day of week (current):
Set day of week
(35) Date/Hours (current):
Set hours
(36) Date/Minutes (current):
Set minutes