Installation & Operation Manual
21
3
General
venting
(continued)
All vent connections MUST be secured
by the vent manufacturer's joint connector
(FIG. 3-9).
NOTICE
DIR #2000543311 00
JOINT CONNECTOR
PVC to POLYPROPYLENE
ADAPTER
Figure 3-9 Near Boiler Polypropylene Venting
Polypropylene
This product has been approved for use with polypropylene
vent with the manufacturers listed in Table 3E.
All terminations must comply with listed options in this
manual and be a single-wall vent offering.
For support and special connections required, see the
manufacturer's instructions. All vent is to conform to standard
diameter and equivalent length requirements established.
When determining equivalent combustion air and vent length
for polypropylene single-wall piping:
•
1 foot of Duravent 4 inch single-wall pipe is equivalent
to 1.6 feet of piping
Flexible polypropylene
For use of flex pipe, it is recommended to have the vent material
in 32°F or higher ambient space before bending at installation.
No bends should be made to greater than 45° and ONLY
installed in vertical or near vertical installations (FIG. 3-8).
Use only the adapters and vent system listed
in Table 3E. DO NOT mix vent systems of
different types or manufacturers. Failure
to comply could result in severe personal
injury, death, or substantial property
damage.
WARNING
Installations must comply with
applicable national, state, and local
codes. For Canadian installation,
polypropylene vent must be listed as
a ULC-S636 approved system.
Installation of a polypropylene
vent system should adhere to the
vent manufacturer’s installation
instructions supplied with the vent
system.
WARNING
Insulation should not be used on
polypropylene venting materials. The use
of insulation will cause increased vent wall
temperatures, which could result in vent
pipe failure.
IMG00840
*NOTES: 1) FLEX PIPE MAY ONLY BE RUN IN A VERTICAL ORIENTATION
2) ALL VENT LENGTHS REPRESENTED IN ABOVE CHARTS ARE
EQUIVALENT LENGTHS.
3) SECTION A IS EQUIVALENT FEET OF RIGID PIPE, WHICH MAY
INCLUDE 45 AND 90° ELBOWS. PLEASE SEE SIZING SECTION
FOR DETERMINING EQUIVALENT FEET.
“B” DIM
3” RIGID 3” FLEX 4” FLEX
Duravent 3”
10 FT
20 FT
30 FT
40 FT
50 FT
60 FT
70 FT
80 FT
90 FT
60 FT
53 FT
47 FT
40 FT
33 FT
27 FT
20 FT
13 FT
7 FT
90 FT
80 FT
70 FT
60 FT
50 FT
40 FT
30 FT
20 FT
10 FT
10 FT
20 FT
30 FT
40 FT
50 FT
60 FT
70 FT
80 FT
90 FT
30 FT
27 FT
23 FT
20 FT
17 FT
13 FT
10 FT
7 FT
3 FT
“A” DIM
“B” DIM
Duravent 4”
“A” DIM
4” RIGID 4” FLEX
“B” DIM
3” RIGID 3” FLEX 4” FLEX
Centrotherm 3”
10 FT
20 FT
30 FT
40 FT
50 FT
60 FT
70 FT
80 FT
90 FT
45 FT
40 FT
35 FT
30 FT
25 FT
20 FT
15 FT
10 FT
5 FT
90 FT
80 FT
70 FT
60 FT
50 FT
40 FT
30 FT
20 FT
10 FT
“A” DIM
10 FT
20 FT
30 FT
40 FT
50 FT
60 FT
70 FT
80 FT
90 FT
33 FT
29 FT
26 FT
22 FT
18 FT
15 FT
11 FT
7 FT
4 FT
“B” DIM
Centrotherm 4”
“A” DIM
4” RIGID 4” FLEX
CHIMNEY
CAP
A
B
90 FT
80 FT
70 FT
60 FT
50 FT
40 FT
30 FT
20 FT
10 FT
5” FLEX
Figure 3-8 Near Boiler Flexible Polypropylene Venting
The installer must use a specific vent starter
adapter at the flue collar connection. This adapter
is supplied by the vent manufacturer to adapt to
its vent system. See Table 3F for approved vent
adapters. Discard CPVC starter piece.
NOTICE
NOTICE
NOTICE
Vent
Diameter
Manufacturer
Model
Type
PVC
Adapter
Adapter
Clamp
Joint
Connector
Sidewall
Kit
2 inch
Centrotherm
Innoflue
Single-Wall / Flex
ISAGL0202
IAFC02
IANS02
ISLTK02*
3 inch
Centrotherm
Innoflue
Single-Wall / Flex
ISAGL0303
IAFC03
IANS03
ISLTK03*
4 inch
Centrotherm
Innoflue
Single-Wall / Flex
ISAGL0404
IAFC04
IANS04
ISLTK04*
2 inch
DuraVent
PolyPro
Single-Wall / Flex
2PPS-ADL
Included
2PPS-LB
2PPS-HLKL*
3 inch
DuraVent
PolyPro
Single-Wall / Flex
3PPS-ADL
Included
3PPS-LB
3PPS-HLKL*
4 inch
DuraVent
PolyPro
Single-Wall / Flex
4PPS-ADL
Included
4PPS-LB
4PPS-HLKL*
Table 3E Approved Polypropylene System Adapters
*The sidewall kit components are only needed if the sidewall termination assembly is used (see FIG. 4-1B on page 23).