50
Installation & Operation Manual
7
Gas connections
Connecting gas supply piping
1. Reference FIG.'s 7-1 and 7-2 to pipe gas to the boiler.
a. Install a field supplied sediment trap / drip leg
upstream of the boiler gas controls.
b. Install a ground joint union for servicing, when
required.
c. Install a manual shutoff valve in the gas
supply piping outside the boiler jacket when
required by local codes or utility requirements.
d. In Canada – When using manual main shutoff
valves, it must be identified by the installer.
DIR #2000543315 00
GAS SUPPLY
DRIP
LEG
MANUAL
SHUTOFF
VALVE
UNION
Figure 7-1 Union Connection and Gas Supply Piping
Do not check for gas leaks with an open
flame – use the bubble test. Failure to
use the bubble test or check for gas leaks
can cause severe personal injury, death, or
substantial property damage.
3. Purge all air from the gas supply piping.
4. Before placing the boiler in operation, check the boiler
and its gas connection for leaks.
a. The appliance must be disconnected from the gas
supply piping system during any pressure testing of
that system at a test pressure in excess of 1/2 PSIG
(3.5 kPa).
b. The appliance must be isolated from the gas supply
piping system by closing a manual shutoff valve
during any pressure testing of the gas supply piping
system at test pressures equal to or less than 1/2 PSIG
(3.5
kPa).
c. The appliance and its gas connection must be leak
tested before placing it in operation.
WARNING
5. Use pipe sealing compound compatible with propane
gases. Apply sparingly only to male threads of the pipe
joints so that pipe dope does not block gas flow.
Failure to apply pipe sealing compound as
detailed in this manual can result in severe
personal injury, death, or substantial
property damage.
Knight Wall Hung Fire Tube boilers
are typically shipped ready to fire on
natural gas. Check boiler rating plate to
determine which fuel the boiler is set for.
If set to natural gas, it may be converted
to LP by installing an LP venturi and any
additional components provided in the LP
conversion kit (Models WH56 - WH286
only) or by installing a propane orifice
(Model WH400 only) (see pages 12 and
13). In order to operate on LP gas, these
components MUST BE installed. Failure
to comply could result in severe personal
injury, death, or substantial property
damage.
WARNING
WARNING
2. Support piping with hangers, not by the boiler or its
accessories.
The gas valve and blower will not support
the weight of the piping. Do not attempt
to support the weight of the piping with
the boiler or its accessories. Failure to
comply could result in severe personal
injury, death, or substantial property
damage.
WARNING