75
Confi guration
Menu item
Action
Choices
Neutral zone
Adjust neutral zone using
keys.
Confirm with
enter
0...10.00 PH
(
01.00 PH
) /
0...2000 mV
Controller: P action
Adjust P action using
keys.
Confirm with
enter
10...9999%
(
0100%
)
Controller: I action
Adjust I action using
keys.
Confirm with
enter
0...9999 SEC
(
0000 SEC
)
Controller: D action
Adjust D action using
keys.
Confirm with
enter
0...9999 SEC
(
0000 SEC
)
Behavior during
HOLD
Select response using
keys.
Confirm with
enter
Y LAST
/ Y OFF