Possible causes
ERR 104 INVALID PARAMETER
CONTROLLER
Configuration error
Controller
ERR 105 INVALID SPAN I-INPUT
Configuration error
Current input
ERR 106 INVALID CHANNEL SELECTION
OUT1/2
Cond-Cond:
Out1/Out2 channel
not assigned (disabled)
ERR 107 INVALID CHANNEL SELECTION
RELAYS
Cond-Cond:
Relay channel not
assigned (disabled)
ERR 108
Cond, CondI, Cond-Cond:
OUT1 INVALID CORNER X/Y
Bilinear curve:
Invalid vertex point
ERR 109
Cond, CondI, Cond-Cond:
OUT2 INVALID CORNER X/Y
Bilinear curve:
Invalid vertex point
ERR 110
CATION EXCHANGER CAPACITY
Capacity of ion exchanger used
up – replace
Sensoface messages:
Cell factor monitoring
SENSOR CELL FACTOR
CALIBRATE OR CHANGE SENSOR
Table monitoring
(TC/Conc/Sal/USP)
OUT OF INTERNAL TABLE
Zero point monitoring
SENSOR ZERO CALIBRATE OR CHANGE SENSOR
Cell factor / zero point
monitoring
SENSOR ZERO/CELL FACTOR
CALIBRATE OR CHANGE SENSOR
Sensor TAG does not corre-
spond to device entry.
WRONG SENSOR TAG
Sensor GROUP does not
correspond to device entry.
WRONG SENSOR GROUP xxxx