NOVAR 2100/2200 Operating Manual
capacitor replacement you can clear the counter by its editing and selection the
C
L
r
option.
The value is taken in account during power factor control intervention evaluation in order the
capacitors to be loaded as uniformly as possible.
4.3.4.6 Fan / Heater Temperature Thresholds, No. 29 ÷31
If any of three upper outputs are set to the fan or heater control state, these parameter groups bear
specification of the temperature range when the corresponding output to be closed or open.
Otherwise, the parameter group is hidden.
The relation of the parameters is as follows :
•
parameter No. 29 … the
ultimate
output thresholds (for example, output 2.9 for models 2100
R18 )
•
No. 30 … the
penultimate
output thresholds (output 2.8)
•
No. 31 … the
antepenultimate
output thresholds (output 2.7)
For other models, the relation is analogous : for example, for the “2100 R15” models, corresponding
outputs are 2.6/ 2.5 / 2.4.
Each of the parameter group contains :
•
switch-on threshold in line 2, marked with symbol ▲
•
switch-off threshold in line 3, marked with symbol ▼
On the example at left we can see :
•
thresholds for the penultimate output (probably set as
heater), i.e. the output 2.8 for „2100 R18“ models
•
the output 2.8 will be closed as soon as temperature drops
downto -15°C
•
the output will be opened as soon as temperature reaches -
5°C
4.3.4.7 Output Set 2, No. 33
With this parameter you can divide the controller outputs into two so called “sets”. Then some output
parameters can be specified individually for each of the sets.
As default,
the
Set 2
parameter is
Off
. In such case all of outputs are comprised into
set 1
and
the set
2
does not exists.
The output set 2
parameter can be set to any outputs from No. 1.2 up. If, for example, set to the output
No.
1.7
, two sets are defined :
•
set 1
comprises 6 outputs from No.
1.1
through
1.6
•
set 2
comprises outputs from
1.7
up, i.e. remaining (at maximum) 18 outputs No. 1.7
through 1.9, 2.1 through 2.9 and 3.1 through 3.6
In other words
the set 2
parameter defines beginning output of the set 2.
For now, only
the discharge time
parameters can be set individually for the two sets. There can be
more of such parameters in the next firmware versions.
43
Fig. 4.10 :
Heater Temperature
Thresholds