NOVAR 2100/2200 Operating Manual
Tab. 4.3 : PFC Control Setup Parameters
#
parameter group
range
default
comment
01 target PF & bandwith, tariff 1
line 2 : target PF (cos/tan/φ)
line 3 : control bandwith
- 0.80 ÷ 0.80 (cos)
0.000 ÷ 0.040 (cos)
(cos)
0.98
0.010
Other available formats :
„tan“, „φ“. Toggled with the
key.
02 control time UC/OC, tariff 1
line 2 : c. time at undercompensation (UC)
line 3 : c. time at overcompensation (OC)
5 sec ÷ 20 min
5 sec ÷ 20 min
3 min
30 sec
No “L”: control time reduction
by squared proportion
“L”: linear c. time reduction
03 offset power, tariff 1
any
0
Value corresponds to U
NOM
specified; p Displayed when
offset control
set only.
05 tariff 2 control & actual tariff
line 2 : actual tariff (state)
line 3 : tariff 2 control
t=1 / t=2
OFF / dig. input (InP)
/ power (P)
OFF
Actual tariff is not any
presetable parameter; it
indicates actual tariff state
only
06 target PF & bandwith, tariff 2
line 2 : target PF (cos/tan/φ)
line 3 : control bandwith
- 0.80 ÷ 0.80 (cos)
0.000 ÷ 0.040 (cos)
(cos)
0.98
0.010
Other available formats :
„tan“, „φ“. Toggled with the
key.
07 control time UC/OC, tariff 2
line 2 : c. time at undercompensation (UC)
line 3 : c. time at overcompensation (OC)
5 sec ÷ 20 min
5 sec ÷ 20 min
3 min
30 sec
No “L”: control time reduction
by squared proportion
“L”: linear c. time reduction
08 offset power, tariff 2
any
0
Value corresponds to U
NOM
specified; p Displayed when
offset control
set only.
10 tariff 2 control power
0 ÷ 120 % P
NOM
0
Displayed when
tariff 2
control
set to
power
only.
11 control strategy
3p+1p (31P) /
3p (3P) /
3*1p (1P)
3p+1p
(31P)
12 choke control & choke control limit PF
line 2 : choke control
line 3 : choke control limit power factor
OFF / mixed (M) /
non-mixed (nM)
- 0.80 ÷ 0.80 (cos)
OFF
1.0
Choke control limit power
factor displayed when
choke
control
set to
mixed
only.
13 offset control
OFF / On
OFF
4.3.3.2 Control Bandwidth on High Loads for Tariff 1/2, No. 01/06
The parameter is displayed in the line 3. Using it you can specify the control bandwidth on high loads
(see Figure 4.6). The value entered specifies the range of reactive power in the C zone which
constitutes condition considered as compensated, making the controller stop control interventions.
Fig. 4.6 : Standard Control Bandwidth
34