It is then possible to control the coupled boiler using the temperature set on the
AUX thermostat
; above the set
temperature the coupled boiler turns off and comes on again only below the set temperature.
-
VALVE:
Connect terminals 6, 7 and 8 to the three-way motorised valve.
This is used to control a motorised three-way valve (or two motorised two-way valves) installed on the DHW system.
The valve opens the DHW circuit on the wood-burning appliance at temperatures higher than those set on the
VALVE thermostat
(230V voltage on terminals 6 and 7) and closes the DHW circuit at lower temperatures (230V
voltage on terminals 7 and 8). (Terminals already connected at the factory to a cable suitable for connection to a
three-way valve).
-
SERV:
Connect terminals 9 and 10. This is to control an additional pump installed inside the appliance. The
additional pump will operate at temperatures higher than those set on the
SERV thermostat
. If connected to an
additional pump, we recommend setting the
SERV
thermostat to temperatures no lower than 55°C to prevent the
formation of condensation, which would damage the appliance's boiler unit.
-
LIGHT:
Connect terminals 11 and 12 to the light inside the oven.
This is to control the oven light. The oven light is
operated by holding down the button for 5 seconds
P4 (Set).
(Terminals already connected to the oven light in the
factory).
-
PUMP:
Connect terminals 13 and 14 to the pump on the heating system.
This is used to control the pump installed
on the heating system. The heating pump will operate at temperatures higher than those set on the
PUMP
thermostat
. We recommend setting the pump thermostat to temperatures higher than 55°C to prevent the formation
of condensation, which would damage the appliance's boiler unit. (Terminals already connected to pump cable in the
factory).
-
PROBE:
Connect the water temperature probe to terminals 18 and 19. This is to monitor the temperature of the
water inside the appliance. If the probe is not connected, the control unit's display shows
“Lo”
; if there is a short-
circuit in the probe, the display shows
“Hi”.
(Terminals already connected to H2O Probe in the factory).
-
LEVEL:
Connect the level switch (water level sensor) to terminals 20 and 21. This is to signal the water level in the
boiler unit of the appliance is low. (Terminals already connected to level switch in the factory).
HYDRAULIC CONNECTION
The plumbing connections must be made in a rational way using the connections on the template of the appliance.
To facilitate the connection of the pipes, all the plumbing connections have been fitted in the technical compartment,
leaving space to make the appropriate connections.
To access the unit and to make the necessary plumbing connections, proceed as follows:
2
1
LH side
LH technical compartment
Содержание ALTEA 110
Страница 1: ...ENGLISH Wood burning boiler cooker ALTEA 110 SICURO TOP INSTALLATION USE MAINTENANCE AND HELPFUL TIPS ...
Страница 2: ......
Страница 11: ...WOOD BURNING BOILER COOKER ALTEA 110 SICURO TOP 8 EN Rev 1 2 Overall dimensions ...
Страница 39: ...WOOD BURNING BOILER COOKER ALTEA 110 SICURO TOP 36 EN Rev 1 2 ...
Страница 40: ...Cod CS IST ALT110TOP EN KLOVER Srl Via A Volta 8 37047 San Bonifacio VR VAT No 02324280235 www klover it ...