DOCUMENTATION OF AUTOMATIC CONTROL
FOR COMPACT UNITS
DTR.MCKT-HPX.
AUT-009.5.0
PAGE
GDYNIA
MCKT-HPX
2016
31/35
KLIMOR Spółka z ograniczon
ą
odpowiedzialno
ś
ci
ą
, 81-035 Gdynia, ul. B. Krzywoustego 5
Fax: (+48 58) 783-98-88; Tel.: (+48 58) 783-99-99
Service – Fax: (+48 58) 783-98-88; Tel.: (+48 58) 783-99-50/51 Mobile: (+48) 510 098 081
Information provided in this document is subject to change
email:
– Office
– Service
Register
address
Code
Description
Type
40019
AIR
EXHAUST_
MANUAL
MSB: Air exhaust fan RPM setting {0-255}
Change possible from
the
BMS/Readout
level
TSET
LSB: Setting of the TSET requested temperature using the
ModBus [°C],
{0-50}
Change possible from
the
BMS/Readout
level
40020
TOCHRONY
MSB: [SICE_SEL][x][Tochr5][Tochr4] [Tochr3][Tochr2][Tochr1]
[Tochr0]
SICE_SEL:
Selection of sensor for anti-frost protection algorithm
0 – To
1 – Tn
[Tochr5]:[Tochr0]
Protection threshold temperature [°C],{0-50}
Change possible from
the
BMS/Readout
level
---
---
Read only
40030
H2TzEN
MSB: [x][x][H2TzEn5][H2TzEn4][H2TzEn3] [H2TzEn2][H2TzEn1]
[H2TzEn0]
[H2TzEn5]:[H2TzEn0]
External temperature, above which the secondary heater will not
receive the operation permit [°C],{0-30}
Read only
CTzEN
LSB: [x][x][CTzEn5][CTzEn4][CTzEn3]
[CTzEn2][CTzEn1][CTzEn0]
[CTzEn5]:[CTzEn0]
External temperature, below which the cooler will not receive the
operation permit [°C],{0-35}
Read only
40031
OUTE
MSB: Analog output OUTE {0-255}
Read only
OUTF
LSB: Analog output OUTF {0-255}
Read only
40032
AIN0
MSB: 0÷10V analog input at the UNIBOX3v41 controller PCB {0-
255}
Read only
UI1
LSB: UI1 0÷10V analog input at the UNIBOX_EXTENDER_v1.1
controller PCB {0-255}
Read only
40033
UI2
MSB: UI2 0÷10V analog input at the UNIBOX_EXTENDER_v1.1
controller PCB {0-255}
Read only
PuTzOn
LSB: [PuTzON_EN][x][PuTzOn5][PuTzOn4][PuTzOn3][PuTzOn2]
[PuTzOn1][PuTzOn0] [PuTzOn5]:[PuTzOn0]
External temperature of starting the water heater pump. The pump
always operates below the indicated temperature, independent of
the operation mode and heat demand [°C], {0÷30}, (0xBF mask)
PuTzON_EN – pump operation permit in the Tz temperature
function
Read only
40034
THiConst
MSB: Upper limit of air supply temperature (adjustment against
Tn2) [°C], {0÷50}
Read only
TLoConst
LSB: Lower limit of air supply temperature (adjustment against
Tn2) [°C], {0÷50}
Read only