8.
DANFOSS FC 51 INVERTERS FOR MCKT-HPX 3
Basic parameters for programming Danfoss FC 51 inverter.
Settings for adjusting speed by analogue 0÷10V signal
Sample setting for the motor and converter 0,75kW/1×230V
Parameter
no.
Parameter name
Entered
data
Unit
QUICK
MENU 1
120
Motor rated power
0.75
kW
122
Motor rated voltage
400
V
123
Motor rated frequency
50
Hz
124
Rated motor current
2
A
125
Motor rated RPM
1450
RPM
129
Auto matching with AMT motor
Switch on [2]
302
Min set Hz value
10
Hz
303
Max set Hz value
50
Hz
341
Acceleration time in s from min to max Requested value
30
s
342
Breaking time in s from min to max Requested value
30
s
MAIN
MENU
190
Motor thermal protection
ETR Trip 1 [4]
412
Motor low speed limit in Hz
10
Hz
414
Motor high speed limit in Hz
50
Hz
416
Limit of torque in %
110
%
610
Terminal 53 Low voltage level
0.07
V
611
Terminal 53 High voltage level
10
V
614
Terminal 53 Minimum set value
10
Hz
615
Terminal 53 Maximum set value
50
Hz
*/ After setting this parameter to function [2] there will be the PRESS HAND START message displayed on the
screen. When the HAND START button on the control panel is pressed, the converter proceeds with the auto
matching. When the auto matching is complete, press OK on the control panel and the parameter is automatically set
to [0] value. Now you can proceed with the programming.
The User Manual of the FC 51 inverter and the full programming manual can be found at the manufacturer's website:
http://www.danfoss.com/Poland/BusinessAreas/DrivesSolutions/frconverters/VLT+Micro+Drive.htm