DOCUMENTATION OF AUTOMATIC CONTROL
FOR COMPACT UNITS
DTR.MCKT-HPX.
AUT-009.5.0
PAGE
GDYNIA
MCKT-HPX
2016
12/35
KLIMOR Spółka z ograniczon
ą
odpowiedzialno
ś
ci
ą
, 81-035 Gdynia, ul. B. Krzywoustego 5
Fax: (+48 58) 783-98-88; Tel.: (+48 58) 783-99-99
Service – Fax: (+48 58) 783-98-88; Tel.: (+48 58) 783-99-50/51 Mobile: (+48) 510 098 081
Information provided in this document is subject to change
email:
klimor@klimor.pl
– Office
serwis@klimor.pl
– Service
Digital inputs
Status indication of the Unibox digital inputs and Extender [0|1] module:
{DI2}
– input 0 (DI0) – not used
{DI1}
– input 1 (DI1) – pressure gauge of low pressure
{DI1}
– input 2 (DI2) – pressure gauge of air supply/exhaust filter
{DI3}
– input 3 (DI3) – fire alarm
{DI4}
– input 4 (DI4) – pressure gauge of high pressure
{DI5}
– input 5 (AIN0) – fan inverter alarm
{DI6}
– input 6 (AIN1) – preliminary heater alarm
Analog inputs
Indication of analog inputs:
[AIN0]
– fan inverter alarm
[AIN1]
– preliminary heater alarm
6.1.3.3 OUTPUTS
Digital outputs
Indicating the status of the Unibox relay outputs [0|1]:
{DO1}
– relay 1 (OUTPUT1) – solenoid valve 1
{DO2}
– relay 2 (OUTPUT2) - 4-way valve
{DO3}
– relay 3 (OUTPUT3) – air supply/exhaust dampers
{DO4}
– relay 4 (OUTPUT4) – heat pump compressor
{DO5}
– relay 5 (OUTPUT5) – solenoid valve 2
//DIGITAL
OUTPUTS
DO1=_
DO2=_
DO3=_
DO4=_
DO5=_
OUTPUTS
Digital ►
Analog ►
PWM ►
//WE.ANALOG.
AIN0=00%
AIN1=00%
//DIGITAL INPUTS
DI0=_
DI1=_
DI2=_
DI3=_
DI4=_
DI5=_
DI6=_