DOCUMENTATION OF AUTOMATIC CONTROL
FOR COMPACT UNITS
DTR.MCKT-HPX.
AUT-009.5.0
PAGE
GDYNIA
MCKT-HPX
2016
15/35
KLIMOR Spółka z ograniczon
ą
odpowiedzialno
ś
ci
ą
, 81-035 Gdynia, ul. B. Krzywoustego 5
Fax: (+48 58) 783-98-88; Tel.: (+48 58) 783-99-99
Service – Fax: (+48 58) 783-98-88; Tel.: (+48 58) 783-99-50/51 Mobile: (+48) 510 098 081
Information provided in this document is subject to change
email:
– Office
– Service
Communication
[CtrlCOM2, CtrlCOM3]
– selection of remote or local control using COM2/COM3 port:
{Loc}
– local control with use of the DEN16-C panel; possibility of reading data via MODBUS
{Rem}
– remote control, possibility of writing and reading data via MODBUS
[COM2, COM3]
– {YES|NO} enables switching on communication with the use of the COM2/COM3 port and the
MODBUS RTU (RS485) data bus.
[BR2]
– {9600|19.200} data transmission speed for COM2 (can only be changed in the STOP mode) [bits/s]
[BR3]
– {9600|19.200|57.600|115.200} data transmission speed for COM3 (can only be changed in the STOP mode)
[bits/s]
[WifiPIN]
– 4-digit PIN of the wireless communication module
The menu is available after entering the factory password
6.1.3.5 ADVANCED SETTINGS
Inputs
[DI0f]:[DI6f]
–
selecting alarm message displayed for the digital input’s signal:
{DIN}
– digital input, no message
\\*INPUTS
DI0f=Din
S=_ R=_
DI1f=LoP
S=_ R=_
DI2f=Flt
S=_ R=_
DI3f=POZ
S=_ R=_
DI4f=HiP
S=_ R=_
DI5f=VAL
S=_ R=_
DI6f=!HE
S=_ R=_
AINfn=__
/ADVANCED SETTINGS
Inputs ►
Fan
►
Sensors
►
Temp control ►
Heat recovery►
Heat pump ►
Time blocks ►
Auto Stop ►
Factory settings
►
//Communication
CtrlCOM2=___
COM2=___
BR2=_____
CtrlCOM3=___
COM3=___
BR3=_____
WifiPIN=____