36
EVO-S COMPACT
COMPACT AIR HANDLING UNIT
OPERATION AND MAINTENANCE MANUAL
The devices should be stored in covered and closed rooms.
The units should be protected against unauthorized access.
The devices should be stored on an even surface, which pre-
vents the construction from moving and, as a consequence,
unsealing the unit.
3.2 Assembly of the units
The units should be installed in covered and closed rooms
(the exception is the roof version of the units), meeting the
requirements resulting from the general safety regulations.
These should be separate and closed rooms, inaccessible to
the unauthorized persons, with ventilation ensuring at least
one air exchange per hour.
Moreover, the rooms should be free of chemical pollution,
smoke and dust, and the internal temperature in winter
conditions should not be lower than +5˚C, and in summer
not higher than +40˚C.
Installation of the air handling units in the open air or in a
room with a lower temperature should be agreed with Kli-
mer at the design and equipment selection stage.
3.2.1 Unit frame
Table 6
Unit frame dimensions
EVO Unit
size
Type of the frame
Maximum
cross-wise support
spacing*
Sheet
thickness
Frame-
work
height*
5100, 3200,
0300,
channel frame
(optional founda-
tion corners).
1500 mm
2 mm
120 mm
0400, 2500,
0600,
channel frame
1500 mm
2 mm
120 mm
0700, 5800,
0010, 5310,
5610,
channel frame
1500 mm
2,5 mm
120 mm
*For longer sections, additional horizontal supports are
used at the centre resulting from the length dimensions.
Fig. 12
Spacing of the central units’ foundation corners
Fig. 13
Dimensions of the frame from bent channel bars
The dimensions marked with the equality sign are equal.
Their maximum length is given in the table above. For the
rotary heat exchanger block, the supports or frames are lo-
cated in the outline of the frames or supports of the other
unit blocks (it may occur that the rotary heat exchanger ho-
usings extend beyond the outline of the frame or supports).
In case of AHU foundation:
The air-handling units must be placed in accordance with
the frame contour, taking into account the cross supports
according to the figure of the frame.
Dimension x on the drawings given in the 6. Local support
of the control panel monoblocks is allowed provided that:
a) for air handling units (small where feet may be present)
the support area must not be smaller than 200x200 and
located in all places where these elements occur Fig. 14,
Fig. 15.
Fig. 14
AHU on foundation corners
Fig. 15
The unit on the foundation corners with central support
Any damage resulting from improper trans-
portation, unloading and storage is not co-
vered by the warranty and claims will not be
considered by KLIMOR.
Содержание EVO-S COMPACT
Страница 2: ...SERWIS SERVICE 4858 7839950 51 48 510098081 serwis klimor com...
Страница 30: ...SERWIS SERVICE 48 587839950 51 48 510098081 seriws klimor com...
Страница 58: ...SERWIS SERVICE 48 587839950 51 48 510098081 serwis klimor com...
Страница 59: ...EVO S COMPACT KLIMOR...
Страница 65: ...63 7 8 9 10 11 50 DN40 11...
Страница 67: ...65 b 200x200 16 17 16 17 c 200x200 300x200 18 18 3 2 2 EVO 2000 5100 5610 19 13 M12 M12 M12 19...
Страница 68: ...66 EVO S CO CT 2900 a 50 20 b 150 21 c 22 2900 b c...
Страница 69: ...67 3 3 23 13 24 5100 0720 25 26 3 4 3 4 1 110 3 4 2 7 kW 3 3 15 15 30 30 P 11 P 16 P 21 P 29 3 4 8...
Страница 75: ...73 31 32 30 10 20 1 100 C 2 3 32 4 5 DX 0 03 4 5 2 12 12 4 5 3 DX...
Страница 76: ...74 EVO S CO CT CHA 4 5 4 34 4 5 5 35 4 5 6 DX 36 DX MHA...
Страница 81: ...79 5 6 6 1 KT 7 EVO wzgl dnie zmia 11 PN EN13779 2008 12 2000 24 4000 24 4000 6 12 plug fan 30 C 130 C 4...
Страница 82: ...80 EVO S CO CT 8 19 1 2 3 DX 4 5 6...
Страница 84: ...82 EVO S CO CT c IP54 d e 41 1 1 42 f A IP65...
Страница 85: ...83 11...
Страница 86: ...SERWIS SERVICE 48 587839950 51 48 510098081 serwis klimor com...
Страница 87: ......