32
EVO-S COMPACT
COMPACT AIR HANDLING UNIT
OPERATION AND MAINTENANCE MANUAL
Tabl. 1
Basic EVO-S COMPACT parameters
Unit size
Width
Height
Width (*)
Framework
height
Air flow min.
Air flow max.
[mm]
CPR-C
CPR-P
RR
[m
3
/h]
KLIMOR EVO-S COMPACT 5100
700
950
2760
1790
1900
120
778
2722
KLIMOR EVO-S COMPACT 3200
950
950
2760
1790
1900
120
1102
3856
KLIMOR EVO-S COMPACT 0300
950
1150
3150
2030
2100
120
1408
4927
KLIMOR EVO-S COMPACT 0400
1200
1150
3150/3450 2030/2180
2100/2400
120
1822
6376
KLIMOR EVO-S COMPACT 2500
1300
1350
3430/3730 2310/2460
2100/2400
120
2419
8467
KLIMOR EVO-S COMPACT 0600
1300
1550
3570/4120 2450/2700
2100/2600
120
2851
9979
KLIMOR EVO-S COMPACT 0700
1500
1550
4120
2700
2600
120
3326
11642
KLIMOR EVO-S COMPACT 5800
1500
1850
4200/4600 2880/3130
2400/2800
120
4082
14288
KLIMOR EVO-S COMPACT 0010
1700
1850
4400/4900 3030/3380
2600/3350
120
4666
16330
KLIMOR EVO-S COMPACT 5310
1800
2350
5170
3700
2800
120
6487
22705
KLIMOR EVO-S COMPACT 5610
2000
2550
5170/5670 3700/3950
2800/3350
120
7934
27770
*maximum length of the basic system depending on the selected
fan size (without additional functions)
If an electric heater or a single- or double-row water heater
is selected, the heater will be installed in the space of the
inter-changeable current exchanger without affecting the
length of the basic unit. In a unit with a rotary exchanger,
the basic unit will be extended. Heaters with more rows are
treated as additional functions and are available in separate
sections.
The above mentioned flow values refer to the cross-section
inside the unit.
ΔP
– available pressure 0÷500/1000 Pa
Selection of AHU size is dependent on the air flow through
the filters, cooler, humidifier, AHU pressure drop and noise
level. It is possible to manufacture air handling units with
different air flow rate and pressure than those specified
in Table 1. The above mentioned flow values apply to the
AHU window. For water heaters, do not exceed the speed
of 4,5 m/s in the exchanger window, and for coolers 3,5 m/s.
2.2.2 Optimal parameters of heating, cooling and humidifying
mediums
Table 2
Medium parameters
PARAMETERS
UNIT
VALUE
Evaporation temperature of the cooling gas
˚
C
+7
Temperature of the cooling water (glycol solution) at the
inflow:
- minimum
- maximum
˚
C
˚
C
+2
+12
Maximum temperature of heating water:
- hot
˚
C
95
Recommended available pressure:
- for a water cooler with a control node
- for a water heater with a control node
MPa
MPa
0,05÷0,1
0,01÷0,05
2.2.3 KLIMOR EVO AHU designation method
KLIMOR EVO units are normally designated by an abbrevia-
ted code according to the designation in diagram 1.
Diagram 1
Short designation of KLIMOR EVO AHUs
1
2
3
4
5
EVO-S
Compact
SIZE:
5100, 3200, 0300,
0400, 2500, 0600,
0700, 5800, 0010,
5310, 5610
AIRFLOW
DAMPER
V/100*
AVAILABLE
PRESSURE
ΔP/10*
PAGE
VERSIONS:
R – RIGHT
L _ LEFT
(*) airflow rate rounded upwards, available pressure rounded
downwards
**) customised sizes of the units
EXAMPLE:
KLIMOR EVO Compact: standard right-hand si-
ded, size 0010, air volume 10000 m
3
/h, available pressure
500Pa.
KLIMOR EVO-S COMPACT 0010 10050R
Full designation of the KLIMOR EVO AHUs includes additio-
nal codes of the air handling sections.
Diagram 2
Extended designation of KLIMOR EVO AHUs
1
2
3
4
5
VERSION:
AIRFLOW RATE
AVAILABLE
PRESSURE STR.
VERSIONS:
SECTION
CODE:
acc. to the
Table 3
FC
ELASTIC
CONNEC-
TION
AD
SHUT-OFF,
REGULATING
DAMPER
OPCJE
O – external
version
CS – Control
system included
EXAMPLE: the KLIMOR EVO AHU in standard right-side
version with complete control system, size 0010, air flow:
10,000 m
3
/h, available pressure: 500 Pa, equipped with the
cartridge filter, water heater, water cooler, fan, heat recovery
cross-flow exchanger and connectors
KLIMOR EVO-S COMPACT 0010 10050RPFCPRWHVF-
FCAD/10050LPFCPRVFFCADCS
Содержание EVO-S COMPACT
Страница 2: ...SERWIS SERVICE 4858 7839950 51 48 510098081 serwis klimor com...
Страница 30: ...SERWIS SERVICE 48 587839950 51 48 510098081 seriws klimor com...
Страница 58: ...SERWIS SERVICE 48 587839950 51 48 510098081 serwis klimor com...
Страница 59: ...EVO S COMPACT KLIMOR...
Страница 65: ...63 7 8 9 10 11 50 DN40 11...
Страница 67: ...65 b 200x200 16 17 16 17 c 200x200 300x200 18 18 3 2 2 EVO 2000 5100 5610 19 13 M12 M12 M12 19...
Страница 68: ...66 EVO S CO CT 2900 a 50 20 b 150 21 c 22 2900 b c...
Страница 69: ...67 3 3 23 13 24 5100 0720 25 26 3 4 3 4 1 110 3 4 2 7 kW 3 3 15 15 30 30 P 11 P 16 P 21 P 29 3 4 8...
Страница 75: ...73 31 32 30 10 20 1 100 C 2 3 32 4 5 DX 0 03 4 5 2 12 12 4 5 3 DX...
Страница 76: ...74 EVO S CO CT CHA 4 5 4 34 4 5 5 35 4 5 6 DX 36 DX MHA...
Страница 81: ...79 5 6 6 1 KT 7 EVO wzgl dnie zmia 11 PN EN13779 2008 12 2000 24 4000 24 4000 6 12 plug fan 30 C 130 C 4...
Страница 82: ...80 EVO S CO CT 8 19 1 2 3 DX 4 5 6...
Страница 84: ...82 EVO S CO CT c IP54 d e 41 1 1 42 f A IP65...
Страница 85: ...83 11...
Страница 86: ...SERWIS SERVICE 48 587839950 51 48 510098081 serwis klimor com...