5.  UNIT OPERATION 

The unit is preset with factory default settings and will fulfill the basic needs for inverter-charger 
operation. Display is used to provide information about the unit status and the unit function can be 
customized through the Display.

 

Once the unit function is customized, Display can be removed if desired, as the unit can run without 
the Display. 

Understanding the Indicator and Unit Functions on Display and Main unit 

 

Understanding the Display Push Buttons Functions 

Normal Operation 

Pressing any button illuminates the back lighting of the display for about 10 seconds. 
Display shows Battery Voltage 

‘V’. Can use ‘

’ 

f  and 

’  

g  button to scroll through DC Current 

‘A’, AC Output Power ‘KW’. 

‘Power’

 

d  button (Same function as the 

‘On/Off’ push button on the main unit): 

-  To turn Inverter ON: Press and hold for 3 seconds to turn unit ON. Display will turn ON and is 

followed by a beep. 

-  Display show 

‘-- -- --‘, All icons turn ON, followed by the revision levels of the unit (Rx.x, rx.x) 

Note: When AC Input is available, this Power button cannot be used to turn OFF the unit. 

‘Menu/SET’

 

e  button: 

•  can be used to view the unit setting.

 

‘ESCAPE’ 

h  button:  

- Press and hold for 5 seconds to turn OFF or ON the AC Output Switch. (Use as AC Output 
ON/OFF button). 

Viewing Unit Setting 

‘Menu/SET’

 button: Press once to enter the Unit Functions chart listed below. 

’ & ‘

’ 

Buttons:

 

Use the 

’ & ‘

’ buttons to view other unit functions.

 

‘Escape’ 

Button: Press once to exit viewing of the unit settings. 

Changing Unit Settings 

a) 

At normal operation, press ‘Menu/Set’ once. 

b) Use 

’ & ‘

’ button to select the function that needs to be changed 

c) 

Press and hold ‘Manu/Set’ button until the display flashes, use ‘

’ & ‘

’ button to select the new 

parameters 

Indicator 

Status 

Function 

Power 

ON 

Unit is power ON 

AC Output 

ON 

AC Output is turned ON 

OFF 

AC Output is turned OFF  

Status 

Green 

AC Output is running from Utility 

Green (Flash) 

AC Output is running from utility and battery charger is charging the battery 

Amber 

AC Output is running from Inverter 

Amber 

(Flash) 

Utility is detected and is under verification. AC Output is still running from 
Inverter and will switch to Utility in about 10 seconds. 

Red 

Error/Warning occurs. Display will show Error or Warning code 

Содержание 120V 12V-2000W-80A

Страница 1: ...V 2000W 80A BIC1220080 12V 3000W 100A BIC1230100 24V 2000W 40A BIC2420040 24V 3000W 50A BIC2430050 230V Series 12V 2000W 80A BIC1220080i 12V 3000W 100A BIC1230100i 24V 2000W 40A BIC2420040i 24V 3000W...

Страница 2: ...1363 BIC1220080i AU Inverter Charger 12V 2000W 80A 230VAC Australia Socket NS NZS3112 BIC1230100i EU Inverter Charger 12V 3000W 100A 230VAC Schuko Socket CEE 7 4 BIC1230100i UK Inverter Charger 12V 30...

Страница 3: ...mable fumes or gases such as propane tanks or large engines AVOID covering the ventilation openings Always operate unit in an open area Prolonged exposure to high heat or freezing temperatures will de...

Страница 4: ...Page 4 Table of Contents 1 INTRODUCTION 5 2 PRODUCT DESCRIPTION 5 3 UNDERSTANDING THE UNIT 6 4 INSTALLING THE UNIT 10 5 UNIT OPERATION 13 6 TROUBLESHOOTING 24 7 SPECIFICATIONS 25 8 WARRANTY 27...

Страница 5: ...utility power is interrupted This manual will explain how to use this unit safely and effectively Please read and follow these instructions and precautions carefully 2 PRODUCT DESCRIPTION The Sinewave...

Страница 6: ...follow these instructions can damage the unit and could also result in personal injury or loss of life CAUTION Before beginning unit installation please consider the following The unit should be used...

Страница 7: ...y Actual run times may vary on battery type used b DC Fuse or Circuit Breaker DC rated fuse or DC rated circuit breaker connected along the DC positive line is required Fuse Circuit Breaker Rating 12V...

Страница 8: ...ent sizes refer to the applicable installation code for the DC grounding detail In marine applications the main AC DC ground bonding may require galvanic isolators to avoid galvanic corrosion Check yo...

Страница 9: ...t is used to connect to the Multi Function Display of the unit k Multi Function Display The display is used to provide unit information and for setting and programming the unit l BTS Port The port is...

Страница 10: ...Input terminals will damage the unit and it cannot be repaired Damage caused by reverse polarity connection is not covered by the warranty IMPORTANT Field wiring DC terminals tightening torque 12 13 N...

Страница 11: ...secure the AC Input wire For AC Output Hardwire Connections Insert the AC Input cable through the AC Output Strain relief h on the unit Connect the AC Sub Panel AC Ground wire to the AC Output Ground...

Страница 12: ...rovides AC Input power to the unit If AC input source is available the Status LED amber will flash for about 10 seconds indicating the AC Input source is available It will then turn to solid green or...

Страница 13: ...nput is available this Power button cannot be used to turn OFF the unit Menu SET e button can be used to view the unit setting ESCAPE h button Press and hold for 5 seconds to turn OFF or ON the AC Out...

Страница 14: ...Battery Default Bulk Charge Float Voltage is 14 2V 13 8V Default Flooded Battery Default Bulk Charge Float Voltage is 14 4V 13 5V AGM Battery Default Bulk Charge Float Voltage is 14 3V 13 4V Lithium...

Страница 15: ...the last bar flashing indicates the unit is running in By Pass mode and the battery is in charging process The charging stages are indicated by the number of bars 4 bars in solid indicates the battery...

Страница 16: ...arting Check if any object has blocked the air flow of the unit E05 When unit is in Battery Inverter mode Input battery voltage is low and warning occurs Recharge battery as unit will shutdown shortly...

Страница 17: ...y Note During blackout Power button can be used to temporarily turn inverter Off to save battery power if AC Output power is not required INT ABU Automatic Backup with Charger set to Off CHG OFF By Pa...

Страница 18: ...battery capacity Inverter is disabled Power indicator On AC Output indicator Off AC Output is not available due to the inverter being set to Manual Backup Mode MBU Status indicator Off After 10 secon...

Страница 19: ...acity Inverter is disabled Power indicator On AC Output indicator Off AC Output is not available due to the inverter being set to Manual Backup Mode MBU Status indicator Off After 10 seconds Display a...

Страница 20: ...ON Inverter Only Unit is running as inverter only no By Pass function CHG OFF ON This setting is specially designed so that the AC load connected to AC Output is always getting clean sinewave power f...

Страница 21: ...Switch On Off Status indicator solid green Note Power button function is disabled in this stage Blackout When a blackout occurs unit will not provide AC Backup Display remains On for 10 seconds with...

Страница 22: ...e total AC current draw from the shore power during the By Pass Charger mode to avoid tripping the shore power Branch Breaker Absorption to Float Stage Current Setting 12V 3000W 20A 15A 10A Default 5A...

Страница 23: ...d Battery Disconnect Functions Battery Under and Over Voltage Setting Battery Low Disconnect voltage has selectable range 10 5 12 0V 0 1V steps Default 10 5V The Battery Low Disconnect Voltage has to...

Страница 24: ...utput switch is turned Off Press and hold the ESCAPE button for 5 seconds to turn On the AC Output AC Input Source is available but is out of the acceptance range by the unit Check AC Input Source Uni...

Страница 25: ...rt RJ12 Inverter Mode Battery Voltage DC Current AC Output Power Charger Mode Charging Voltage Charging Current AC Input Power Running as Battery Charger Charging Voltage Range 13 8 14 8 VDC Float Vol...

Страница 26: ...Mode Battery Voltage DC Current AC Output Power Charger Mode Charging Voltage Charging Current AC Input Power Running as Battery Charger Charging Voltage Range 27 6 29 6 VDC Float Voltage Range 26 0 2...

Страница 27: ...e if products are deemed non working or malfunctioning the product may be returned to the purchasing store within 30 days of original purchase Any defective unit that is returned to manufacturer withi...

Отзывы: