21
Scheme with two adjustable heating circuits and the HUW container
2
: 1
–
boiler, 2 - controller, 3 -
boiler temperature sensor, 4 - outside (weather) temperature sensor, 5
–
boiler pump, 6
–
HUW pump, 7 -
mixer valve actuator, 8
–
mixer temperature sensor, 9
–
mixer pump, 10
–
room thermostat, 11
–
HUW
temperature sensor, 12
–
burner feeder (stoker), 13
–
burner fan, 14 - expansion tank, 15 - thermostatic 3-
way valve for return protection, 16
–
HUW tank, 17
–
additional B module, 18
–
heat exchanger
.
RECOMMENDED SETTINGS:
Parameter
Setting
MENU
CH activation temp.
55
C
Service settings
→
CH and HUW settings
Exchanger support
ON
Service settings
→
CH and HUW settings
Mixer 1 support
CH ON
Service settings
→
Mixer 1 settings
Max. mixer 1 temp.
70
C
Service settings
→
Mixer 1 settings
Mixer 1 heating curve
0.8
–
1.4
Mixer 1 settings
Mixer 1 weather control
ON
Mixer 1 settings
Mixer 2 support
Floor on
Service settings
→
Mixer 2 settings
Max. mixer 2 temp.
45
C
Service settings
→
Mixer 2 settings
Mixer 2 heating curve
0.3
–
0.8
Mixer 2 settings
Mixer 2 weather control
ON
Mixer 2 settings
Mixer 1 room thermostat
eSTER T2
Service settings
→
Mixer 2 settings
* when a standard room thermostat with ON-OFF contacts is connected instead of the (10) room
thermostat, select the option for the thermostat =
Universal
or, if the setting is hidden, do not
need to select any option for the thermostat.
2
The presented hydraulic scheme does not replace central heating engineering design and may be used for
information purposes only!