![KIPI ecoMAX360P1-C Скачать руководство пользователя страница 16](http://html1.mh-extra.com/html/kipi/ecomax360p1-c/ecomax360p1-c_installation-and-operating-manual_1971698016.webp)
16
Service settings
→
CH and HUW settings
Settings of time control of circular pump are
analogical to settings of night reductions. In
defined time periods circular pump is
deactivated. In omitted periods the circular
pump is switched into position
Circulating
operation time,
what
Circulating standstill
time
.
8.23
Fuel level configuration
•
Fuel level indicator activating
To activate displaying fuel level following
parameters are to be set
Boiler setting
→
Fuel level
→
Alarm level
o
n value bigger than “0”, i.e. 10%
.
Pressing
or
button in the main
window fuel level is displayed in main
window.
•
Fuel level indicator service
Each time after filling the fuel silo to the
intended level, press the
button for a
longer time - then the prompt "
Set fuel level
to 100%
" will appear. After accepting on
YES
fuel level will be set for 100%.
Tip: Fuel can be refilled anytime, that means
it is not needed to wait till the silo is empty.
However fuel should be filled up to the level
corresponding to 100% and set the controller
level by pressing
button.
•
Description of activity
The controller measured fuel level on the
basis of its current consumption. Factory
settings will not always correspond to actual
fuel consumption, so to work correctly this
method needs level calibration by controller’s
user. No additional fuel sensors are required.
•
Calibration
Fill the fuel silo to the level which
corresponds to full level of fuel, then set
value of parameter:
Boiler settings
→
Fuel level
→
Fuel level
calibration
→
Fuel level 100%
In main window the indicator will be set on
100%. The calibration process is marked
with a pulsating fuel level indicator. The
indicator will pulsate until programming point
referring to minimum fuel level. Decreasing
level of fuel in the silo should be monitored
constantly. When fuel level reaches expected
minimum, parameter value should be set this
way:
Boiler settings
→
Fuel level
→
Fuel level
calibration
→
Fuel level 0%
8.24
Feeder test
The controller allows to test the efficiency of
the burner feeder, which has a significant
impact on the operation of the burner. The
test is started with the
Feeder test
parameter
in the menu:
Boiler settings
→
Feeder
Remove the flexible tube from the burner
and direct its end into a plastic bag. Run the
feeder test. After the test, weigh the fuel and
enter the measured value into the
Fuel dose
from test
parameter in the test.
8.25
Information
Menu
Information
enables
view
to
measured temperatures and allows to check
which of devices are currently activated.
Switching between following screens is done
by pressing
or
button.
After connecting extension B module
of
mixers
information
about
auxiliary mixers are displayed.
8.26
Manual control
In the controller it is possible to manual
activate devices like i.e. pumps, feeder
engine, or blower engine. It enables to check
if the device is operating correctly and if it is
connected properly.
Entering manual control menu is
possible only, when boiler is
switched off.
Содержание ecoMAX360P1-C
Страница 6: ...6 ...
Страница 7: ...USER SETTINGS ecoMAX360P1 C ...
Страница 18: ...18 ...
Страница 19: ...19 INSTALLATION AND SERVICE SETTINGS ecoMAX360P1 C ...
Страница 42: ...42 ...
Страница 43: ...43 ...