38
parameter in the range of 2..6.
Integr. time const.
The greater the value of this parameter, the slower is the actuator reaction for
temperature deviation. Setting too lower values can lead to unnecessary actuator
movements, too high value extending the time needed to find set value of the
temperature. The right value is being edited according to research results. It is
recommended to set this parameter value between 100 and 180.
Valve opening time
Set full valve opening time given at the plate of valve servomotor, i.e. 140 sec.
Pump off by thermostat
Setting the parameter on
YES
value causes closing of mixer servomotor and
deactivating mixer pump after disconnecting contacts of room thermostat. This is not
recommended because the heated room can be too cool.
Mixer input dead zone
Setting parameter determining value of temperature dead zone for mixer controlling
circuit. The controller regulates mixer in such a way to keep the temperature of mixer
cycle equal to preset value. However, avoid too frequent movements of servomotor,
which can shorten its long-life usage. Regulation is undertaken only when measured
temperature of mixer cycle will be higher or lower than preset value by the value bigger
than
Mixer input dead zone
.
14.6
Other parameters
Parameter
Description
Show advanced setup
Options available:
•
YES
- displays hidden parameters which edition is not recommended.
•
NO
- hides hidden parameters.
Service counters
Operating time counter of the controller and the connected devices.
Restore service settings
Restoring service settings settings from main menu are restored.
Save serv.set.
Selecting
YES
saves all service settings after changing the parameters in the service
menu.
Log out
Setting to
YES
will exit the time mechanism of entering the service menu without using
the service password.
Output H (mod B)
The menu contains settings related to the configuration of output H for additional B
module. Options available:
•
OFF
- no support for H output (mod B).
•
Cleaning
- operation of the heat exchanger cleaning mechanism. Cleaning will be
turned on by
Cleaning time
with a cleaning break in
Cleaning pause
.
•
Alarm
- when an alarm occurs, the output H (mod B) is switched on.
•
Reserve boiler
- the output H (mod B) controls the reserve boiler.