background image

24

LOGF30 LOG INSTALLATION

1) Align front hole of log support
plate with original log locator pin.
2) Slide log support over pin & using
two 6-32 x 5/16 screws, mount plate
to burner grate.

NOTE:

Make sure log support is tight
against side of burner grate before
fastening.

LOG LOCATOR TAB

LOG SUPPORT

ORIGINAL LOG

LOCATOR PIN

6-32 x 5/16 screws

For use in ZVF52 Firebox only

Содержание ZVF33

Страница 1: ...cause injury or property damage Refer to this manual for correct installation and operational procedures For assistance or additional information consult a quali ed installer service agency or the gas...

Страница 2: ...2...

Страница 3: ...utes each firing and a 5 minute cool down between each Be aware during log and firebox paint curing that a white deposit may be developing on the inside of the glass doors It is important to remove th...

Страница 4: ...ors 16 Installing 17 Installation Clearances 17 Installing by Framing Fireplace 18 Installing Firebox Using Optional Pre Built Mantel Cabinets 19 Installing Gas Line 20 Installing Burner Systems into...

Страница 5: ...22 000 32 000 5 5 10 1 6 3 5 35 0 218 ZVFB3633MVP Millivolt Liquid Propane 22 000 33 000 11 13 6 3 10 51 Full Open ZVF52 Vent Free Firebox Required Burner system Select from below to complete the repl...

Страница 6: ...ches paper garbage or any other material on top of logs or logs into ame 5 Warning Always operate appliance with front replace screens closed 6 Make sure any safety screen or guard removed for servici...

Страница 7: ...any part has been under water Immediately call a quali ed service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water WARN...

Страница 8: ...ray 36VF 106 the two leads from the blower that attach to the thermodisc must be attached together and the thermodisc can be discarded See page 35 for wiring The replace hood is packaged on top of the...

Страница 9: ...ING SPECIFICATIONS ZVF33 FIREPLACE AND FRAMING DIMENSIONS FIGURE 1 ZVF33 Framing Clearances to Fireplace Bottom 0 Sides 0 to standoffs Top 0 to standoffs Adjacent side wall 6 Front of replace to ceili...

Страница 10: ...m 0 Sides 0 to standoffs Top 0 to standoffs Adjacent side wall 6 Front of replace to ceiling 41 36 17 36 33 7 8 34 36 3 8 17 28 7 16 10 1 4 36 36 3 8 10 1 4 40 3 16 NAILING TABS 17 34 17 33 7 8 0 5 fo...

Страница 11: ...Sides 0 to standoffs Top 0 to standoffs Adjacent side wall 6 Front of replace to ceiling 41 17 42 42 36 36 1 4 42 3 8 17 NAILING TABS 30 11 16 9 1 2 9 1 2 42 42 3 8 61 5 16 43 3 8 17 1 2 for gyprock...

Страница 12: ...s Adjacent side wall 6 Front of replace to ceiling 41 INSTALL GAS LINE FROM THIS SIDE 20 898 52 000 44 0 FLAME PATTERN 44 375 5 062 6 250 20 898 GAS LINE LOCATED ON OPPOSITE SIDE AS SHOWN Minimum encl...

Страница 13: ...atmosphere have a continuous water vapor retarder with a rating of one perm 6 x 10 11 per pasec m2 or less with openings gasketed or sealed and b weather stripping has been added on openable windows...

Страница 14: ...ors and vents to the outdoors 4 Compare the maximum Btu Hr the space can support with the actual amount of Btu Hr used __________________ Btu Hr maximum the space can support __________________ Btu Hr...

Страница 15: ...e within 12 of the oor on the wall connecting the two spaces You can also remove door into adjoining room Follow the National Fuel Gas Code NFPA 54 ANSI Z223 1 Section 5 3 Air for Combustion and Venti...

Страница 16: ...12 of the ceiling and one within 12 of the oor Connect these items directly to the outdoors or spaces open to the outdoors These spaces include attics and crawl spaces IMPORTANT Do not provide openin...

Страница 17: ...inches These reboxes can be installed as freestanding units against a wall with the approved optional cabinet mantels or as a built in unit The clearances are the same for either installation method N...

Страница 18: ...5 If using optional Brass Surround Kit install the trim after nal nishing and or painting of wall See instructions included with brass trim accessory for attaching Surround 6 Install and properly tes...

Страница 19: ...rly test gas log heater Follow installation instructions included with the vent free gas log heater that is being installed NOTICE A quali ed service person must install rebox Follow all local codes N...

Страница 20: ...the pilot outlet Make sure that the pressure tap is completely closed after checking gas pressure The pressure should be checked with the appliance burning and the control set on high IMPORTANT Loose...

Страница 21: ...echnician 1 Remove replace hood and door Refer to Installation of Door and Hood page 33 2 Remove log set handling carefully by holding gently at each end Refer to Log Placement Gloves are recommended...

Страница 22: ...CE LOG SET CROSSOVER LOG RETAINER PINS 4 PIECE LOG PLACEMENT 1 Place Front main Log on locator pins 2 When installing 4 piece log set with rear log separate position rear main log on rear log holder l...

Страница 23: ...r and Locator Pin and lower into position STEP 3 Place flat surface of bottom of log onto burner assembly base and push log up to logs 1 and 2 STEP 4 Position log 4 onto rear log holder and pull up to...

Страница 24: ...g locator pin 2 Slide log support over pin using two 6 32 x 5 16 screws mount plate to burner grate NOTE Make sure log support is tight against side of burner grate before fastening LOG LOCATOR TAB LO...

Страница 25: ...on support bracket and lower into position STEP 4 Place rear log onto rear log holder and pull up to left and right front logs STEP 5 6 Line up holes on crossover logs with locator pins on rear log 4...

Страница 26: ...derside of Log C Place log over front burner and locator pin then lower into position as illustrated Step 3 Locate hole on the underside of Log D Place log over front burner and locator pin then lower...

Страница 27: ...27 Step 5 Place log A onto rear log holder and pull up to log C D LOGF18 PLACEMENT GUIDELINES continued...

Страница 28: ...e front main log A on log locator pins Retainer pin Step 3 Position rear main log B onto rear log holder located on rear of rebox Position locking tabs of rear main log B into locking tabs of front ma...

Страница 29: ...29 Step 5 Place Log C onto front burner LOGF24 PLACEMENT GUIDELINES continued...

Страница 30: ...urner grate NOTE Make sure log support is tight against side of burner grate before fastening Log Locator tabs Log locator pin Rear log holder Grate Bars Step 3 Place front log by positioning the notc...

Страница 31: ...pull up to the left and right front logs Step 7 Line up left crossover log with locator pins and lower into position Step 8 Line up right crossover log with locator pins and lower into position Comple...

Страница 32: ...32 CAUTION Do not wire 120 Volt power to Millivolt switches or thermostats MILLIVOLT LIGHTING INSTRUCTIONS...

Страница 33: ...Ref C Loosen installed 1 2 DT screws with 1 4 wrench Slide slotted area of hood under screws 2 Tighten screws to nish installation OPTIONAL FIXED SCREEN DOOR 1 Remove curtain system and hood if insta...

Страница 34: ...The end of panel with tightened screw can now be slid into teardrop hole Ref A 4 Align opposite side of panel with teardrop Ref A and tighten screw A small wrench may be required to hold nut 5 Ref B f...

Страница 35: ...ocation for THERMO DISC WARNING Label all wires prior to disconnection when servicing controls Wiring errors can cause improper and dangerous operation Verify proper operation and servicing WARNING El...

Страница 36: ...33VF P627SI Rate Screw Manual Ref Part Numbers for No ZVFB3330MAN ZVFB3330MAP Description 12 33VF P8213 33VF P8402 ODS Pilot 13 33VF P522SI 33VF P522SI ODS Valve 14 24GL 104 24GL 104 Valve Bracket 17...

Страница 37: ...for No ZVFB3330MVN ZVFB3330MVP Description 10 33VF 113 33VF 113 ODS Shield 12 33VF P8214 33VF P8404 ODS Pilot 13 33VF P637SI 33VF P636SI ODS Valve 14 6000 112 6000 112 Valve Bracket 15 1000 214 1000 2...

Страница 38: ...17SI 33VF P627SI Rate Screw Manual 12 33VF P8213 33VF P8402 ODS Pilot Ref Part Numbers for No ZVFB3633MAN ZVFB3633MAP Description 13 33VF P522SI 33VF P522SI ODS Valve 14 24GL 104 24GL 104 Valve Bracke...

Страница 39: ...rs for No ZVFB3633MVN ZVFB3633MVP Description 10 33VF 113 33VF 113 ODS Shield 12 33VF P8214 33VF P8404 ODS Pilot 13 33VF P637SI 33VF P636SI ODS Valve 14 6000 112 6000 112 Valve Bracket 15 1000 214 100...

Страница 40: ...VF 113 Pilot Bracket Ref Part Numbers for No ZVFB5240MVN ZVFB5240MVP Description 12 33VF P8214 33VF P8404 ODS Pilot 13 33VF P637SI 33VF P636SI ODS Valve 14 6000 112 6000 112 Valve Bracket 15 1000 214...

Страница 41: ...F P522SI 33VF P522SI ODS Valve 14 24GL 104 24GL 104 Valve Bracket 16 33VF P617SI 33VF P627SI Rating Screw 17 33VF P603VE 33VF P603VE Compression Sleeve 3 16 18 33VF P613VE 33VF P613VE Compression Nut...

Страница 42: ...VF P8214 33VF P8404 ODS Pilot 13 33VF P637SI 33VF P636SI ODS Valve 14 6000 112 6000 112 Valve Bracket 15 1000 214 1000 214 Piezo 17 33VF P603VE 33VF P603VE Compression Sleeve 3 16 18 33VF P613VE 33VF...

Страница 43: ...nd Chrome Cover New Style 31 3 16 H x 36 5 8 W Z6SPB Surround Polish Brass Cover New Style 31 3 16 H x 36 5 8 W ZVF33DS Door Frame c w Fixed Screen Z33FK Fan Kit w Variable Wall Mount Speed Control Te...

Страница 44: ...i Lo Flame Adjustment Millivolt Only Z36RL Refractory Liner 3 Piece ZVF42U KINGSMAN ZERO CLEARANCE VENT FREE FIREBOX w BOTTOM PAN Listed for USA as a Universal Firebox Framing 42 3 8 W x 36 1 4 H x 17...

Страница 45: ...7 000 BTU HR Liquid Propane BURNER WITH GRATE Bottom Firebox Pan Required when used with models ZVF52 Valve located underneath burner assembly GLVF24MAN Vent Free Gas Log Burner Manual Valve 35 000 BT...

Страница 46: ...FF position Possible Cause Remedy 1 Gas leak 1 Locate and correct all leaks 2 Control valve defective 2 Replace control valve When Igniter button is pressed there is a spark at ODS pilot but no igniti...

Страница 47: ...er is damaged 2 Replace burner 3 Gas regulator is defective 3 Replace gas regulator Slight smoke or odor during initial operation Possible Cause Remedy 1 Vapors from paint or curing process of logs 1...

Страница 48: ...th service or maintenance h damage repairs inoperation or inefficiency resulting from faulty installation or application i electricity or fuel costs or any increase in electricity or fuel cost whatsoe...

Отзывы: