Chapter 6 List of Parameters
72
Function
code
Name
Descriptions
Unit
Factory
setting
Modif.
Setting
range
b3.18
b3.29
Input parameter mapping
1 12
Input parameter mapping 1 12
1
0
O 0 1000
Group b4.Keyboard parameters
b4.00 Key-lock function
selection
0: The keys on the operation panel are
not locked, and all the keys are usable.
1: The keys on the operation panel are
locked, and all the keys are unusable.
2: All the keys except for the
multi-functional key are unusable.
3: All the keys except for the SHIFT key
are unusable.
4: All the keys except for the RUN AND
STOP keys are unusable.
1
0
O 0 4
b4.01 Multi-function key
definition
0: Jog function
1: Coast-to-stop
2: Stop in shortest time
3: Switch of input method of operating
command
4: Switch forward/reverse.
(Save after power failure)
5: Switch forward/reverse.
(Not save after power failure)
1
0
O 0 3
b4.02 Parameter protection
0: All parameters are allowed
modifying;
1: Only A0.03 and b4.02 can be
modified;
2: Only b4.02 can be modified.
1
1
O 0 2
b4.03 Parameter initialization
0: parameter adjustable
1: Clear fault information in memory
2: Restore to factory settings
1
0
X 0 2
b4.04 Parameter copy
0: No action
1: parameters upload
2: parameters download
3: parameters download (except the
parameters relatedto drive type)
Note:
parameters.
1
0
X 0 3
b4.05 Display parameters
selection
Binary setting0:
No display
1: Display
:
BIT0: Output frequency (Not display
when VFD stop,Display grid frequency
input in energy feedback mode)
1
1007H
O 0 FFFFH