Chapter 6 List of Parameters
65
Function
code
Name
Descriptions
Unit
Factory
setting
Modif.
Setting
range
63: Keyboard potentiometer
64: DI
65: Percentage of host(0 4095)
66 88: Reserved
A6.28 Max. output pulse
frequency
0.1 100.0(Max.100.0k)
0.1kHz
10.0
O 1 1000
A6.29 Center point of pulse
output selection
0: No center point
1: Center point mode 1, the center point
is (A6.26)/2.It is positive when
frequency less than center point.
2: Center point mode 2.The center point
is (A6.26)/2.It is negative when
frequency less then center point.
1
0
O 0 2
A6.30 Functions of terminal AO1 0: No function
1: Output frequency
(0 Max. output frequency)
2: Preset frequency
(0 Max. output frequency)
3: Preset frequency(After Acc/Dec)(0
Max. output frequency)
4: Motor speed(0 Max. speed)
5: Output current(0 2*Iei)
6: Output current(0 2*Iem)
7: Output torque(0 3*Tem)
8: Output power(0 2*Pe)
9: Output voltage(0 1.2*Ve)
10: Bus voltage(0 800V)
11: AI1
12: AI2
13: Keyboard potentiometer
14: DI
15: Percentage of host(0 4095)
16 36: Reserved
1
0
O 0 36
A6.31 Functions of terminal A02 Same as above.
1
0
O 0 36
A6.32 Gain of A01
0.0% 200.0%
0.1%
100.0%
O 0 2000
A6.33 Zero offset calibration of
A01
-100.0% 100.0%
0.1%
0.0
O 0 2000
A6.34 Gain of A02
0.0% 200.0%
0.1%
100.0%
O 0 2000
A6.35 Zero offset calibration of
A02
-100.0% 100.0%
0.1%
0.0
O 0 2000
A6.36 AI1 filter
0.01 10.00s
0.01s
0.05
O 1 1000
A6.37 AI2 filter
0.01 10.00s
0.01s
0.05
O 1 1000
A6.38 Keyboard potentiometer
filter
0.01 10.00s
0.01s
0.05
O 1 1000
A6.39
AI Analog offset calibration
0 1
1
0
O 0 1
Содержание FV20 Series
Страница 47: ......
Страница 48: ...K2M19 1809...