Chapter 6 List of Parameters
62
Function
code
Name
Descriptions
Unit
Factory
setting
Modif.
Setting
range
A6.07 Reserved
-
1
0
O 0 65535
A6.08 Terminal filter
0 500ms
1
10
O 0 500
A6.09 Terminal control mode
selection
0: 2-wire operating mode 1
1: 2-wire operating mode 2
2: 3-wire operating mode 1
3: 3-wire operation mode 2
4: 2-wires operation mode 3
1
0
X 0 3
A6.10 Max. frequency of input
pulse
0.1 100.0(Max.100k), Only valid when
X6 is defined as pulse input.
0.1kHz
10.0
O 1 1000
A6.11 Center point of pulse
setting selection
0: No center point
1: Center point mode 1,the center point
is(A6.10)/2.It is positive when
frequency less than center point.
2: Center point mode 2.The center point
is (A6.10)/2.It is negative when
frequency less then center point.
1
0
O 0 1
A6.12 Filter of pulse input
0.00 10.00s
0.01s
0.05
O 0 1000
A6.13 Input
and negative logic
Binary setting
0: Positive logic.Terminal Xi is
enabled if it is connected to
corresponding common terminal, and
disabled if it is disconnected.
1: Negative logic.Terminal Xi is
disabled if it is connected to
corresponding common terminaland
enabled is it is disconnected.
:
BIT0 BIT3.X1 X4
:
BIT0 BIT1.X5 X6
1
00
O 0 FFH
A6.14 Bi-direction pen-collector
output terminal Y1
0: Running signal(RUN)
1: Frequency arriving signal(FAR)
2: Frequency detection threshold
(FDT1)
3: Frequency detection threshold
(FDT2)
4: Overload detection signal(OL)
5: Low voltage signal(LU)
6: External fault stop signal(EXT)
7: Frequency high limit(FHL)
8: Frequency low limit(FLL)
9: Zero-speed running
10: Terminal X1(Reserved)
11: Terminal X2(Reserved)
12: PLC running step complete signal
1
0
X 0 20