Take the Output Positive from
first
Module and Output Negative from the
last
Module.
7.
Automatic Safety Shutdown:
The Module will automatically shut down under any excessive use conditions in order to prevent damage to
itself and to the connected equipment. Specified limits for excessive current, high voltage and low voltage are
provided in Module’s technical data sheet.
Cause of
Shutdown
LCD Warning Message
Description
Over-Current (OCD)
When the Module has an Over-current
fault, the counter counts for 5 seconds and
if the current does not drop lower than the
cut-off and count down has reached to
zero, the buzzer alarms and the electronic
switch will shut-down.
Caution!
Charge all the Modules to 100% SOC or same voltage level before
connecting them in Series.
Note!
Switch ON the bypass Circuit breaker when connecting in Series, otherwise
it will damage the electronic switch.
Note!
Modules cannot be connected in series-parallel combination under any
circumstance.
Caution!
The Bypass circuit breaker is not protected with electronic switch, therefore
during over-voltage, under voltage and high temperature conditions, the
terminal will not shutdown. It only gives protection for over current
condition.