Sirius Capacitor Module
–
User Manual
Model Number -7100-48-B-2C-M-SD-A-G
This manual is subject to change without notice and at the sole discretion of Kilowatt Labs, Inc.
Kilowatt Labs, Inc. |
21
5.
Recovery Procedure:
When the Module voltage drops below a certain threshold, the control electronics turn
OFF
. To restart the
control electronics, follow the steps below.
1.
Use the Bypass circuit breaker to turn the Module
ON
as shown below.
2.
A power supply having voltage range of 44V
dc
to 54V
dc
and current range of 1A to 10A will be required.
3.
Connect the
positive
terminal of the power supply to the
positive
terminal of the F12 terminal and
negative
terminal of the power supply to the
negative
terminal of the F12 terminal.
4.
Move the lock screw of the Bypass Circuit breaker upward with the help of screw driver.
5.
Once the connection is done, turn
ON
the circuit breaker as shown below. The Module will recharge and
the control electronics will turn
ON
.
6.
The event may take several minutes depending on the power supply used.
Note!
Please read the Application manual to configure the software thoroughly.
The Application manual is downloaded automatically when you install
SiriusVIEW application.