Preparation | Connecting the Power Cord
Connection procedure
1
Check that the AC power line meets the nominal input rating of this product.
The product can receive a nominal supply voltage in the range of 200 Vac to 240 Vac at 50 Hz or 60
Hz.
2
Check that the POWER switch is turned off.
3
Remove the terminal block cover from the AC INPUT terminal block.
4
Connect the power cord to the AC INPUT terminal block.
Be sure to connect the L, N, and
(GND) of the AC input terminal block correctly.
5
Attach the terminal block cover that you removed in step 3.
Put back the AC INPUT terminal block cover by securing it at the lower holes with the screws
attached to it.
6
Attach an appropriate crimping terminal to the switchboard end of the power cord.
The included power cord has a crimping terminal on the PFX2731S end but has no terminal on the
switchboard end. Attach a crimping terminal that is appropriate for the screw on the switchboard
that you are connecting to. Have a qualified engineer perform the work.
7
Turn off the switchboard’s circuit breaker.
8
Connect the L, N, and
(GND) wires of the power cord to the matching terminals
on the switchboard.
GND
AC INPUT terminal block
L: Black or brown
N: White or blue
Terminal block
cover
(GND): Green or green and yellow
Screws (3-M4),
Tightening torque: 1.2 N
・
m