4-4 Remote Control
PAS SERIES
Pin No.
Signal Name
Description
18
CV STATUS
Turns ON during CV operation (open collector output by a photo-
coupler)
*2
19
CC STATUS
Turns ON during CC operation. (open collector output by a photo-
coupler)
20
ALM STATUS
Turns on when OVP, OCP, or OHP is activated or when a shutdown
signal is input.,(open collector output by a photocoupler, held for
approx. 0.5 s when the POWER switch is turned off)
21
OUT ON
STATUS
Turns on when OUTPUT is turned on.
(open collector output by a photocoupler)
22
PWR OFF
STATUS
Turns on when the internal sub power supply is activated with the
POWER switch turned off. (open collector output by a photocou-
pler, held for approx. 0.5 s)
23
SER OUT+
Positive electrode output terminal during master-slave series operation.
24
PRL OUT+
Positive electrode output terminal during master-slave parallel operation.
25
SER OUT-
Negative electrode output terminal during master-slave series operation.
26
PRL OUT-
[COMP OUT]
Negative electrode output terminal during master-slave parallel
operation.
[Compensation signal output terminal during master-slave parallel
operation]
*1.
Items inside brackets are for the 160 V, 320 V, and 500 V models.
*2.
Open collector output (maximum voltage of 30 V and maximum current of 8 mA).
It is insulated from the control circuit.
Содержание PAS 10-105
Страница 10: ...VIII PAS SERIES This page has been intentionally left blank ...
Страница 54: ...3 22 Basic Operation PAS SERIES This page has been intentionally left blank ...
Страница 78: ...4 24 Remote Control PAS SERIES This page has been intentionally left blank ...
Страница 131: ...PAS SERIES Specifications 8 13 This page has been intentionally left blank ...
Страница 137: ...PAS SERIES Specifications 8 19 This page has been intentionally left blank ...
Страница 145: ......