24
Keysight M9514A Site Preparation and Installation Guide
Connect the Chassis to the AC Power Line
Connecting Power to the Chassis
Connecting Power to the Chassis
The M9514A comes prewired for a 3-phase Wye with Neutral configuration for
use with 220/380V, 230/400V, and 240/415C AC lines. Please consult Agilent
Support if you need otehr power entry configurations.
It is your (the end user) responsibility to provide the power cord from the AC
mains disconnect to the chassis. An IEC 60309 (3P+N+E, 6H red) receptacle is
installed on the chassis for quick connect/disconnect to the AC mains.
Four power cords are available from Agilent for the M9514A:
–
Y1235A for 1-phase, no Neutral, 250VAC, NEMA L6-30P, 2.5 M (8.2 feet)
1
–
Y1236A for 3-phase, Wye with Neutral, 240/415VAC, IEC 60309, 2.5 M
(8.2 feet)
1
–
Y1237A for 3-phase, Delta/Wye, no Neutral, 250VAC, NEMA L15-30P, 2.5
M (8.2 feet)
1
–
Y1238A for 3-phase, Wye with Neutral, 240/415VAC, Stripped End, 2.5 M
(8.2 feet)
1
Refer to
, “Power Cords,” starting on page 43 for detailed information
about the Agilent power cords.
An IEC 60309 (3P+N+E, 6H Red) plug is installed on the chassis at the factory.
This can be used for connecting the above Agilent power cords, or you may wire
your own as described in this chapter.
The IEC 60309 connector (3P+N+E, 6H Red) is a common connector for
connecting 400 V, 3-phase power lines. The five pins in the connector are
positioned in a circle with the earth ground (E) as the larger diameter pin. Refer
to the following diagram:
1 These are the AC power cord ratings, not the AC power ratings for the M9514A chassis. The Agilent M9514A
chassis AC input is rated to 240 VAC line-to-line. See Appendix A for cord information.
Содержание M9514A
Страница 1: ...Keysight AXIe 14 Slot Chassis M9514A SitePreparationand Installation Guide...
Страница 2: ......
Страница 6: ...vi...
Страница 14: ...16 Keysight M9514A Site Preparation and Installation Guide Introduction Plan the Chassis Installation...
Страница 37: ...Keysight M9514A Site Preparation and Installation Guide 39 Service and Support Additional Information...
Страница 40: ...42 Keysight M9514A AXIe 14 Slot Chassis Safety Related Specifications...
Страница 44: ...46 Keysight M9514A Site Preparation and Installation Guide Power Cords...