4.11 Stoker emptying time
– this parameter specifies time needed for removal of
the whole fuel from the stoker. Stoker emptying during extinguishing of feeder,
feeding initial fuel dose (portion), and during burner shut down. This setting is
unavailable if the stoker is switched off.
4.12 Auger ignition test
– this parameter provides functionalities of „X” emergency
input. If „NO” setting was selected then „X” input will be used for connection of e.g.
auger flap opening contact sensor or the contact informing on operation of auger
motor overload switch. If „YES” setting was selected then „X” input will be used for
connection of auger temperature sensor used for ignition detection.
CAUTION!
In case emergency input is not used, „NO” parameter shall be selected
in „Auger ignition test” setting and contacts of „X” input shall be closed.
4.13 Auger ignition temperature
– this parameter specifies auger temperature,
when the controller activates auger ignition alarm. This parameter is unavailable
when „NO” was selected in „Auger ignition test” setting.
5.x Ignitor working parameters.
5.1 Flame detector type
– FD–1/ CT–1/2/ PT–1000 – flame detection may follow
with two methods: burner temperature measurement or brightness measurement. In
case when temperature sensor is used, depending on its location, temperature
measurement range may be from several degrees to several hundred degrees. If
measured temperatures do not exceed 100°C it is recommended to use CT-1 or
CT-2 sensor. In case of higher temperatures, PT-1000 sensor shall be used. For
flame brightness measurement, FD-1 optical detector shall be used.