26
5.8 Test the temperature of the fuel shortage
– This parameter determines the
temperature to which must reduce the boiler water temperature to the regulator be-
gan testing the fuel shortage.
5.9 Fuel shortage testing time
– parametr ten określa, przez ile czasu od rozpo-
częcia testowania braku opału temperatura wody w kotle musi być niższa niż od
temperatury ustawionej w parametrze TEMPERATURA TESTU BRAKU OPAŁU, aby
regulator wywołał alarm.
5.10 Firing stabilization
– this parameter determines whether the fuel kindling
Stabilization mode is enabled firing.
5.11 Firing stabilization time
– this parameter determines the maximum operating
time of stabilization firing. This parameter is not available if the parameter
STABILIZATION OF FIRING is set to NO.
5.12 Smooth stabilization of ignition
– setting the parameter to YES will cause the
stabilization of firing up the controller gradually increases the amount of fuel fed.
This parameter is not available if the parameter STABILIZATION OF FIRING is set to
NO.
5.13 Furnace extinction (shut down) time
– if the controller switches to extinction
(shut down) mode, the induction fan is activated according to power selected in „Fan
speed at extinction (shut down)” setting. After burner extinction (flame loss), the fan
operation follows according to time programmed in this setting. This function
ensures combustion of all fuel remains and burner cool down.