25
EN
PHOTOCELL ALARM/SAFETY EDGE
Phototest fail outcome.
EPH
1. Check the photocell and the safety edge connections.
2. Check that the photocells and the safety edg are operating correctly.
ENCODER ALARM
Encoder encoder (only if encoder is present)
EEN
1. Check the encoder connections.
2. Check that the encoder are operating correctly.
After eliminating the cause of the alarm, to delete all errors
simply press the “DOWN -” button or press the SBS (STEPPING)
The first time the control unit is powered up, an autolearning procedure must be carried out to acquire fundamental parameters such as
the travel stroke length and deceleration points.
A transmitter can be “learned” via the specific programming menu or by remote memorisation, using a previously memorised
transmitter.
All the main parameters are set with the default settings by the control unit. To customise the installation, proceed as described in point
4.5 below.
command.
The display returns to the normal screen.
Press “UP“ to read the following parameters on display.
DISPLAY
MEANING
Status display (
--
,
OP
,
CL
,
SO
,
ecc..)
Description of the control unit (--, OP, CL, SO, ecc..)
Maneuvers performed
Counter displays alternating the thousands (without dots) and the units (with dots).
Motor current [A]
Current absorbed by the motor
4.3 - Autolearning of the travel stroke
4.4 - Learning a transmitter
AUTOLEARNING OF THE TRAVEL STROKE AND MAIN PARAMETERS
The decelerations will be those set in the menu, with the same percentage during both opening and
closing.
1. Release the gate or door, move it onto the central position and lock it in place again.
MENU
SBS
DOWN
UP
--
2. Hold down the + and MENU buttons SIMULTANEOUSLY for more than 5 seconds, until the screen
shows LOP and get ready to press the DOWN button (see illustration) if necessary.
3. If the first operation is NOT opening of the gate, press the DOWN button to stop the autolearning.
Then press SBS to restart the acquisition: the gate starts moving again, in the right direction. The motor
opens the gate at low speed to the opening limit switch. On reaching the opening limit switch, the gate
restarts in the closing direction at low speed until it reaches the closing limit switch, displaying LCL.
4. Perform a number of opening, closing and sudden stop commands to ensure that the system is solid
with no assembly defects.
MEMORISING A REMOTE CONTROL
If you are in programming mode exit pressing the MENU button until
--
appears. Press the DOWN (RADIO)
button for more than 2 seconds. Until the display shows the word “rad” (radio), then release the button
1. Press and release the DOWN (RADIO) button a number of times equal to the number of the output to be
activated: once for output STEP BY STEP, twice for output PARCIAL, three times for output ONLY OPEN,
four times for output LIGHT ON/OFF, five times for output PRESET (button 1 = output 1, button 2 = output
2, button 3 = output 3, button 4 = output 4)
+
+
2. The KEY LED will flash a number of times equal to the number of the output selected, with 1 second
pauses between flashes
+ 1s
+ 1s
3. Press the button of the remote control to be memorised within 7 seconds, holding it down for at least 2
seconds
2 s
4. If the memorisation has been successful, the KEY LED will give one long flash
>3s
5. To memorise another remote control on the same output, repeat point 3
N.B If no commands are given for 7 seconds, the receiver automatically quits the programming mode