B-34
BOP-1K 031912
B.139 SYSTem:PASSword:NEW COMMAND
SYST:PASS:NEW
Syntax
:
Short Form: SYST:PASS:NEW <old password>,<new password>
Long Form: SYSTem:PASSword:NEW <old password>,<new password>
Description:
Establishes new password.
The old (current) Main password is checked, then replaced by the new
password. Admin 1 and 2 passwords (PAR. 3.2.4.3) are not available. (See example, Figure B-12.)
See PAR. 3.5.2.2 and Figure 3-16 for special programming considerations.
B.140 SYSTem:PASSword:STATe? QUERY
SYST:PASS:STAT?
Syntax
:
Short Form: SYST:PASS:STAT?
Long Form: SYSTem:PASSword:STATe?
Return Value: <int_value> 0 or 1
Description: Returns a 1 if the password state is enabled or a 0 if it is disabled.
B.141 SYSTem:REMote
COMMAND
SYST:REM
Syntax
:
Short Form: SYST:REM {ON | OFF} or {1 | 0}
Long Form: SYSTem:REMote {ON | OFF} or {1 | 0}
Description:
Used during serial (RS 232) communication to set the unit to remote (1 or ON) or local (0 or
OFF) mode.
This command must be issued prior to commands that affect the power supply output
(e.g., VOLT 10;:OUTP ON) to ensure the unit is in remote mode. See PAR. 3.5.6.3 and Figure B-11.
B.142 SYSTem:REMote? QUERY
SYST:REM?
Syntax
:
Short Form: SYST:REM?
Long Form: SYSTem:REMote?
Return Value: {1 | 0}
Description:
Identifies whether unit it in remote mode (1) or local mode (0) during serial (RS 232) communi-
cation.
See PAR. 3.5.6.3 and Figure B-11.
FIGURE B-11. SETTING THE UNIT TO REMOTE MODE VIA SERIAL (RS 232) PORT
B.143 SYSTem:SECurity:IMMediate COMMAND
SYST:SEC:IMM
Syntax
:
Short Form: SYST:SEC:IMM
Long Form: SYSTem:SECurity:IMMediate
Description:
Initializes all NVRAM variable to factory defaults.
Empties all memory locations. See PAR. 3.5.2.2
and Figure 3-16 for special programming considerations. This command is password protected (must
be preceded by SYST:PASS:CEN (see PAR B.137).
*IDN?
Unit responds with KEPCO,BOP 50-20,E1234,1.66 (typical).
OUTP?
Unit responds with 0 indicating output is off
SYST:REM?
Unit responds with 0 indicating unit is in local mode.
SYST:REM 1
Puts unit in remote mode.
OUTP ON
Enables output
OUTP?
Unit responds with 1 (output on).
SYST:REM 0
Unit set to local mode.
Содержание BOP-MG
Страница 2: ......
Страница 10: ......
Страница 20: ...x BOP 1K 031912 FIGURE 1 1 HIGH POWER BOP SERIES POWER SUPPLY...
Страница 37: ...BOP HIPWR 031912 1 17 FIGURE 1 3 BOP OUTPUT CHARACTERISTICS...
Страница 53: ...BOP HIPWR 031912 2 15 FIGURE 2 4 PARALLEL CONFIGURATION LOCAL SENSING TYPICAL...
Страница 54: ...2 16 BOP HIPWR 031912 FIGURE 2 5 PARALLEL CONFIGURATION REMOTE SENSING TYPICAL...
Страница 64: ......
Страница 132: ......
Страница 192: ......