3-37
3.4
ANALOG REMOTE MODE PROGRAMMING
The BOP can be programmed remotely using analog signals applied to the remote Analog I/O
port at the rear panel (see Figure 2-1 and Table 2-10). Analog remote programming allows the
user to 1) establish voltage or current mode (PAR. 3.4.2), 2) control the main channel using the
BOP as a power amplifier (PAR. 3.4.3) and 3) establish the protection limits (PAR. 3.4.4). An
output signal proportional to output current is also provided for external use (PAR. 3.4.5).
3.4.1
REMOTE OUTPUT OFF
There are two ways two turn off the output using remote signals: (1) Remote Shutdown which
requires the unit to be turned off, then on in order to restore operation and (2) Remote Standby
which sets the output to OFF, putting the unit in STANDBY status.
3.4.1.1
REMOTE SHUTDOWN
A standalone unit can be shut down using a remote signal applied to the PROTECTION EXT.
PORT as shown in Figure 3-12 or 3-13. A multiple unit configuration (parallel, series or series-
parallel) can be disabled by applying a remote signal to the master PAR/SER PROTECTION
PORT as shown in Figure 3-12 or 3-14. When the signal is momentarily active (minimum 100
µ
S
), power transfer between input and output is stopped (both input and output internal modules
are shut off). This condition is latched and requires the unit to be turned off, then on again to
restore normal operation.
Unit in STANDBY - Please Change
Output must be on for the waveform to be executed. press
STANDBY
key to set output on
then press
$
to run the waveform
Can not delete Single Segment - use
F1 to Change
Waveform must have at least one segment.
Can not delete the empty segment.
“End of Segments” was highlighted when
#
- Erase was pressed. Move highlight to valid
segment and try again.
Entry not Empty, Use F1 to change.
@
pressed while a previously saved waveform was highlighted. Use
!
to modify or
highlight Empty and press
@
for a new waveform.
Under Minimum allowed value
Frequency or period was too small.
Frequency has no sign
+/- key is not functional when modifying frequency.
Use F5 to stop waveform.
$
not valid when waveform already executing.
TABLE 3-14. ERROR MESSAGE EXPLANATIONS (CONTINUED)
ERROR MESSAGE
EXPLANATION
Содержание BOP-MG
Страница 2: ......
Страница 10: ......
Страница 20: ...x BOP 1K 031912 FIGURE 1 1 HIGH POWER BOP SERIES POWER SUPPLY...
Страница 37: ...BOP HIPWR 031912 1 17 FIGURE 1 3 BOP OUTPUT CHARACTERISTICS...
Страница 53: ...BOP HIPWR 031912 2 15 FIGURE 2 4 PARALLEL CONFIGURATION LOCAL SENSING TYPICAL...
Страница 54: ...2 16 BOP HIPWR 031912 FIGURE 2 5 PARALLEL CONFIGURATION REMOTE SENSING TYPICAL...
Страница 64: ......
Страница 132: ......
Страница 192: ......