PROGRAMMING/DISPLAY CHARACTERISTICS (Continued)
Trigger Port (See Table 2-3)
Shutdown (pin 2) :
Operation of pin 2 is controlled by OUTP:CONT command (see Par. B.15).
Settings are STANDBY (default), HIGH, LOW, OFF. Either OFF or STANDBY is
required if using OUTP ON and OUTP OFF commands to control the output.
STANDBY (default) External Trigger Shutdown (Isolated
input. Logic 0 or short-circuit causes
the output to go to STANDBY (off,
disabled) (latched status)
Pulse width: 100
µ
S min.
Action delay: 200 mS max
Restore operation by pressing
STANDBY
key.
or sending OUTP ON command via remote
interface.
HIGH Isolated Input for controlling output
status, on or off. High or open (not
connected), output is on (enabled).
When 0 volts or short circuit applied
to the pin, output is off (disabled)
Pulse width: 6 mS min for any guaranteed
unit response.
Action delay: 200 mS max
LOW Isolated Input for controlling output
status, on or off. Logic 0 = output is
on (enabled); Logic 1 or open (not
connected) = output is off (disabled).
Pulse width: 6 mS min for any guaranteed
unit response.
Action delay: 200 mS max
OFF Trigger port disabled. Inputs applied
to pin 2 have no effect.
External Trigger
Input (pin 4)
Isolated input for trigger events
Pulse width: 100
µ
S min.
Action delay: 500
µ
S max
Digital control
local
Panel-mounted keypad
Direct Entry
remote
IEEE 488-2 (GPIB)
SCPI
remote
RS 232
remote
RS 485 (BITBUS)
Used for series and parallel configurations.
Display
front panel
4" backlit LCD displays all functions
remote
All parameters read back on GPIB or RS 232 buses
FUNCTION GENERATOR CHARACTERISTICS
(See PAR. 3.3.9)
Maximum number of waveforms
Local: 16
Remote: 1
Local: Saved for power-up
Remote: Lost when the unit is turned off, must
be saved on the host computer)
Maximum number of segments or basic wave-
forms per waveform
Local: 10
Remote: 126
Or maximum number of points (whichever
comes first)
• The time interval for each segment
depends on the type of waveform: period
for ramp and square waveforms, period or
fraction of period for sine and triangular
waveforms and time interval for DC levels
• Segments that cause the waveform to
exceed the maximum number of points are
not executed. For local operation they are
marked with a triple asterisk on the front
panel. For remote operation an error mes-
sage is generated.
TABLE 1-2. BOP GENERAL SPECIFICATIONS (Continued)
SPECIFICATION
RATING/DESCRIPTION
CONDITION
Содержание BOP-MG
Страница 2: ......
Страница 10: ......
Страница 20: ...x BOP 1K 031912 FIGURE 1 1 HIGH POWER BOP SERIES POWER SUPPLY...
Страница 37: ...BOP HIPWR 031912 1 17 FIGURE 1 3 BOP OUTPUT CHARACTERISTICS...
Страница 53: ...BOP HIPWR 031912 2 15 FIGURE 2 4 PARALLEL CONFIGURATION LOCAL SENSING TYPICAL...
Страница 54: ...2 16 BOP HIPWR 031912 FIGURE 2 5 PARALLEL CONFIGURATION REMOTE SENSING TYPICAL...
Страница 64: ......
Страница 132: ......
Страница 192: ......