5

WIRING

(continued)

AC / DC Power Connections

NOTE:  Connect power only after other connections are finished.  Do not touch the live AC power terminals!  The unit has been

designed with an isolated AC input.  Thus, polarity is not a concern for the AC input. Connect AC power to pins 11 and 12.  The chassis

is plastic, therefore earth ground is not used.  For D.C. operation, c 12V to pin 7 and - D.C. to pin 8.

Sensor Connections

These diagrams show how to hook typical input sensors to the unit.  The unit supplies an unregulated 12 Volt (50mA) output to power

these sensors (Pin 7).

A valid pulse is one which makes a transition from the off-state (0 to 1V) to the on-state (4 to 30V):  a positive going edge.  The input

impedance is 10K Ohms to ground.  The unit can be programmed from the front panel for slow switch closure inputs up to 40Hz (select

"Lo CPS"), or solid state switches (select "hi CPS") up to 9.99KHz.  No rear terminal jumpers are required.  Use PNP (sourcing) type

pulsers.

Wiring Terminations:

1- COMMON

2- N.O.(N.C./NPN)

3- COMMON

4- N.O.(N.C./NPN)

5- COUNT

6- START

7- 12VDC OUT/+DC IN

8- -DC (GROUND)

9- STOP/RESET

10- NOT USED

11- A.C. INPUT

12- A.C. INPUT

RELA

YS

A

B

13- V+

14- I SINK

ANALOG

OUTPUT

ON

CAL.

0-20mA

COUNT

SET

OFF

RUN

4-20mA

RATE

RUN

1  2  3  4

ON

SWITCH

1- COMMON

2- N.O.(N.C./NPN)

3- COMMON

4- N.O.(N.C./NPN)

5- COUNT

6- START

7- +12VDC OUT/+DC IN

8- -DC (GROUND)

9- STOP/RESET

10- NOT USED

11- A.C. INPUT

12- A.C. INPUT

RELA

YS

A

B

13- V+

14- I SINK

ANALOG

OUTPUT

ON

CAL.

0-20mA

COUNT

SET

OFF

RUN

4-20mA

RATE

RUN

1  2  3  4

ON

SWITCH

Contact Closure

Input

AC

Power

1- COMMON

2- N.O.(N.C./NPN)

3- COMMON

4- N.O.(N.C./NPN)

5- COUNT

6- START

7- +12VDC OUT/+DC IN

8- -DC (GROUND)

9- STOP/RESET

10- NOT USED

11- A.C. INPUT

12- A.C. INPUT

RELA

YS

A

B

13- V+

14- I SINK

ANALOG

OUTPUT

ON

CAL.

0-20mA

COUNT

SET

OFF

RUN

4-20mA

RATE

RUN

1  2  3  4

ON

SWITCH

Pulse Output

+

PROXIMITY

SENSOR

AC

Power

* Use Pull-Up Resistor For 

   NPN Outputs 4.7K

 Typical

*

Contact Closure Input

Inductive Proximity Sensor Input

Typical Sensor Connections

Magnetic Pickup (30 mV) Pulse Input

1- COMMON

2- N.O.(N.C./NPN)

3- COMMON

4- N.O.(N.C./NPN)

5- COUNT

6- START

7- +12VDC OUT/+DC IN

8- -DC (GROUND)

9- STOP/RESET

10- NOT USED

11- A.C. INPUT

12- A.C. INPUT

RELA

YS

A

B

13- V+

14- I SINK

ANALOG

OUTPUT

ON

CAL.

0-20mA
COUNT

SET

OFF
RUN

4-20mA

RATE

RUN

1  2  3  4

ON

SWITCH

High level voltage pulse

+

Turbine Flowmeter

(preamplifier fitted)

AC

Power

STRIP CHART

RECORDER

-

+

115 VAC
SOLENOID 
VALVE

MOV  
recommended

115 VAC

AC

Power

1- COMMON

2- N.O.(N.C./NPN)

3- COMMON

4- N.O.(N.C./NPN)

5- COUNT

6- START

7- +12VDC OUT/+DC IN

8- -DC (GROUND)

9- STOP/RESET

10- NOT USED

11- A.C. INPUT

12- A.C. INPUT

RELA

YS

A

B

13- V+

14- I SINK

ANALOG

OUTPUT

ON

CAL.

0-20mA
COUNT

SET

OFF
RUN

4-20mA

RATE

RUN

1  2  3  4

ON

SWITCH

Low level mV pulse

Turbine Flowmeter

(without preamplifier)

115 VAC
SOLENOID 
VALVE

MOV  
recommended

115 VAC

High Impedance (4-30VDC) Pulse Input with Analog Output

Typical Flowmeter Connections

1  2  3  4

REAR   VIEW

1  2  3  4  5  6  7  8  9  10  11  12 

13  14 

Analog Out

Setup Switches

Serial Port

ON

Содержание MINI-BATCHER MB2

Страница 1: ...MINI BATCHER INSTALLATION OPERATING INSTRUCTIONS MODELS MB2 99484 9 24 97 KESSLER ELLIS PRODUCTS INDUSTRIAL DYNAMICS CO 1 800 940 0453...

Страница 2: ...THIS PAGE IS BLANK...

Страница 3: ...UT JUMPER SELECTIONS 7 FRONT PANEL OPERATIONS 8 PROGRAMMING FLOW CHART 8 DEFINITIONS OF MENU PROMPTS 9 CALCULATING SCALE FACTORS 11 PROGRAMMING 12 RS232 RS422 INTERFACE CARD OPERATION 17 RS232 RS422 W...

Страница 4: ...THIS PAGE IS BLANK...

Страница 5: ...NOTE Hold either front or remote reset active to inhibit any start inputs Start Front Panel START button Starts batch by energizing Relay A and Relay B if Prewarn selected Remote 4 30 VDC positive edg...

Страница 6: ...front panel Dimensions 3 622 92 1 772 45 3 925 99 7 4 437 112 7 2 625 66 68 587 4 245 107 8 BEZEL GASKET CUSTOMER PANEL Panel Thickness 0 062 1 5 to 0 187 4 7 max SPECIFICATIONS continued The MINI Bat...

Страница 7: ...s than 125 of an inch thick the possibility exists that there will be some flexing Should this flexing occur the resulting deformation of the panel could cause a loss of the water tight seal In case t...

Страница 8: ...r input lines Also keep these input lines isolated from inductive lines from devices drawing heavy loads If there is a possibility of electrical noise we recommend using shielded cable with the shield...

Страница 9: ...C INPUT 12 A C INPUT RELAYS A B 13 V 14 I SINK ANALOG OUTPUT ON CAL 0 20mA COUNT SET OFF RUN 4 20mA RATE RUN 1 2 3 4 ON SWITCH Contact Closure Input AC Power 1 COMMON 2 N O N C NPN 3 COMMON 4 N O N C...

Страница 10: ...is se lected All decimal points are inverted when Grand Batch Total is being displayed Batching After the batcher has been programmed it will operate as follows The unit will reset to 0 count up mode...

Страница 11: ...J2 C J3 O J1 C J2 O J3 C Output Jumper Selections Output Jumper Selections Before making any board modifications be sure power is disconnected and locate the plastic extender to the case at the rear o...

Страница 12: ...N MODE PRGM PRGM PRGM PRGM pre b RUN MODE ENTER ENTER PRGM hi cps lo cps PRGM SECS NNiNS hours PRGM tot preuu PRGM Start Here PROGRAMMING FLOWCHART A STOP RST B C D E ENTER LOCK PRE A PROG VIEW START...

Страница 13: ...here the decimal is desired Changing the decimal will change the decimal location in the counters presets and rate display gr tot GRAND TOTAL This sets the second counter to count the Grand Total ba t...

Страница 14: ...ewed but not changed Start and Stop buttons will still operate CODE LOCK CODE This message code will flash on display for approximately 3 seconds It will be followed by a 5 digit number xxxxx The numb...

Страница 15: ...387 for whole gal Under count set dploc to dplo c to read tenths of gallons Set PRE A at 55 0 Wire Relay A to solenoid valve Conveyer Batching You want to batch the amount of conveyer distance in fee...

Страница 16: ...he digit where the decimal is desired To clear the decimal press the arrow key fur thest to the right PRGM This is the scaling factor for the count input To change press the arrow key under the digit...

Страница 17: ...clear the decimal press the arrow key furthest to the right Press the ENTER key to enter the displayed location This section sets the second counter operation Press the program key to choose GR TOT G...

Страница 18: ...d digits to change Press ENTER to enter displayed value This sets the number of significant figures to be displayed Press the arrow key un der the digit to change Press ENTER to enter displayed value...

Страница 19: ...fter CODE flashes the display will show the existing lock code To change the code press the key under each digit to be changed Press ENTER to enter displayed value see below to turn lock ON or OFF Key...

Страница 20: ...elected This is the duration 01 to 99 99 sec that relay B will remain energized If 00 00 is selected the relay will latch until reset PRE A Preset A Batch Amount The set point at which output A will d...

Страница 21: ...rompt you to choose another baud rate This will occur until a valid baud rate is entered or escape is pressed PARITY Parity is a bit of information that is inserted before the stop bit and is used to...

Страница 22: ...case The terminal addressing the unit must be capable of driving all loads in the loop The input impedance of RS422 is much higher and there should be no problem driving as many as 99 units The trans...

Страница 23: ...it to a computer with RS 422 five connections are needed These connections are Re ceive data A Receive data B Transmit data A Transmit data B and Ground The connections should be made as follows DP 9...

Страница 24: ...alues SWITCH 2 Select Count or Rate SW2 OFF down Analog output follows rate SW2 ON up Analog output follows count SWITCH 3 Select 4 20mA or 0 20mA SW3 OFF down Selects 4 20mA output range SW3 ON up Se...

Страница 25: ...auses the counter to auto reset at the preset 1 The menu flow chart and the setup steps show the setup for units with all of the available options Options not ordered will be suppressed in the program...

Страница 26: ...therwise abused ALL OTHER WARRANTIES EXPRESSED OR IMPLIED ARE EXCLUDED INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE Example MB2 A 3 1 A S...

Отзывы: