background image

20

ANALOG OUTPUT OPTION

Description:

An optional 4-20mA (0-20mA) output has been added to the Minitrol

series.  The output can be programmed to track rate or total.  This

feature is available by adding suffix A to the part number.  Connec-

tions are via a 2 terminal pluggable screw connector.

Connections: 

(see FIG. 1)

PIN13 supplies the 12 to 18 VDC to power the current loop.

PIN14 is the control sink driver

Accuracy:

50uA worst case

Compliance Voltage:

3 to 30 VDC non conductive

Setup:

The optional analog output feature uses 4 dip switches on the back

for setup.  These switches are used as follows:

SW1 -

 View or change "set low" and/or "set high" values

SW2 - 

Select output for rate or total

SW3 - 

Select 4-20mA or 0-20mA

SW4 - 

Calibrate the unit.

After the regular parameters shown in the programming flowchart

have been set, locate the 4 switches on the back of the unit. (see

FIG. 1)

Switch Settings:
SWITCH 1:

  Enter Analog Low & High (normally off)

Switch 1 is used to  load in the low (4mA or 0mA) and/or the high

(20mA) output settings.  With power on, set switch 1 ON (up).

LOW SETTING is viewed or changed by pressing PRE A.  If the

displayed value is correct, press ENTER.  If not, press buttons A

through E to step to the desired value  and press ENTER. (disre-

gard the display which will show the last count reading).

HIGH SETTING is viewed or changed by pressing PRE B.  If the

displayed value is correct, press ENTER.  If not, press buttons A

through E to step to desired value and press ENTER.

Return switch 1 to OFF (down) position, PRE A and PRE B buttons

now function to view or change relay trip values.

SWITCH 2: 

 Select Count or Rate

SW2 OFF (down): Analog output follows rate

SW2 ON (up): Analog output follows count

SWITCH 3: 

 Select 4-20mA or 0-20mA

SW3 OFF (down): Selects 4-20mA output range

SW3 ON (up): Selects 0-20mA output range

SWITCH 4: 

 Calibrate (normally off)

Switch 4 is used for calibration.  Calibration is done at the factory

and should not be needed (see SWITCH 1 to enter high and low

values).   If recalibration is desired, a calibrated 20mA ammeter

with 1uA resolution is needed.  Attach the "+" lead of the meter to

pin 13 and the "-" lead to pin 14.  Set switch 4 ON (up).  The unit

will output approximately 20.000mA and a decimal will light in the

third position.  Read the output using the ammeter.  Press PRE A.

If the display is the same as the ammeter reading, press ENTER.

If not, press buttons A through E to step to ammeter reading and

ENTER. (Disregard display which now shows the last count read-

ing with decimal point in third position)  Return switch 4 to OFF

(down) position.

RS232 & RS422  Operation:

When the unit is suppled with RS232 or RS422, the analog output

"low" and "high" settings can be accessed and changed through

the serial port.  The codes are as follows:

AL  

Unit will display (transmit) analog out "low" value.

AL(S)XXXXX

 Unit will load analog out "low" with entered

number. (S) = space

AH  

Unit will display (transmit) analog out "high" value.

AH(S)XXXXX

 Unit will load analog out "high" with entered

number. (S) = space

FIG. 1

1  2  3  4

REAR   VIEW

1  2  3  4  5  6  7  8  9  10  11  12 

13  14 

Analog Out

Setup Switches

Serial Port

ON

Typical Wiring:

GND

+12V

STRIP CHART

RECORDER

TURBINE FLOWMETER

PULSE OUTPUT

-

+

1- COMMON

2- N.O.(N.C./NPN)

3- COMMON

4- N.O.(N.C./NPN)

5- COUNT

6- START

7- 12VDC OUT/+DC IN

8- -DC (GROUND)

9- STOP / RESET INPUT

10- NOT USED

11- A.C. INPUT

12- A.C. INPUT

RELA

YS

A

B

13- V+

14- I SINK

ANALOG

OUTPUT

Содержание MINI-BATCHER MB2

Страница 1: ...MINI BATCHER INSTALLATION OPERATING INSTRUCTIONS MODELS MB2 99484 9 24 97 KESSLER ELLIS PRODUCTS INDUSTRIAL DYNAMICS CO 1 800 940 0453...

Страница 2: ...THIS PAGE IS BLANK...

Страница 3: ...UT JUMPER SELECTIONS 7 FRONT PANEL OPERATIONS 8 PROGRAMMING FLOW CHART 8 DEFINITIONS OF MENU PROMPTS 9 CALCULATING SCALE FACTORS 11 PROGRAMMING 12 RS232 RS422 INTERFACE CARD OPERATION 17 RS232 RS422 W...

Страница 4: ...THIS PAGE IS BLANK...

Страница 5: ...NOTE Hold either front or remote reset active to inhibit any start inputs Start Front Panel START button Starts batch by energizing Relay A and Relay B if Prewarn selected Remote 4 30 VDC positive edg...

Страница 6: ...front panel Dimensions 3 622 92 1 772 45 3 925 99 7 4 437 112 7 2 625 66 68 587 4 245 107 8 BEZEL GASKET CUSTOMER PANEL Panel Thickness 0 062 1 5 to 0 187 4 7 max SPECIFICATIONS continued The MINI Bat...

Страница 7: ...s than 125 of an inch thick the possibility exists that there will be some flexing Should this flexing occur the resulting deformation of the panel could cause a loss of the water tight seal In case t...

Страница 8: ...r input lines Also keep these input lines isolated from inductive lines from devices drawing heavy loads If there is a possibility of electrical noise we recommend using shielded cable with the shield...

Страница 9: ...C INPUT 12 A C INPUT RELAYS A B 13 V 14 I SINK ANALOG OUTPUT ON CAL 0 20mA COUNT SET OFF RUN 4 20mA RATE RUN 1 2 3 4 ON SWITCH Contact Closure Input AC Power 1 COMMON 2 N O N C NPN 3 COMMON 4 N O N C...

Страница 10: ...is se lected All decimal points are inverted when Grand Batch Total is being displayed Batching After the batcher has been programmed it will operate as follows The unit will reset to 0 count up mode...

Страница 11: ...J2 C J3 O J1 C J2 O J3 C Output Jumper Selections Output Jumper Selections Before making any board modifications be sure power is disconnected and locate the plastic extender to the case at the rear o...

Страница 12: ...N MODE PRGM PRGM PRGM PRGM pre b RUN MODE ENTER ENTER PRGM hi cps lo cps PRGM SECS NNiNS hours PRGM tot preuu PRGM Start Here PROGRAMMING FLOWCHART A STOP RST B C D E ENTER LOCK PRE A PROG VIEW START...

Страница 13: ...here the decimal is desired Changing the decimal will change the decimal location in the counters presets and rate display gr tot GRAND TOTAL This sets the second counter to count the Grand Total ba t...

Страница 14: ...ewed but not changed Start and Stop buttons will still operate CODE LOCK CODE This message code will flash on display for approximately 3 seconds It will be followed by a 5 digit number xxxxx The numb...

Страница 15: ...387 for whole gal Under count set dploc to dplo c to read tenths of gallons Set PRE A at 55 0 Wire Relay A to solenoid valve Conveyer Batching You want to batch the amount of conveyer distance in fee...

Страница 16: ...he digit where the decimal is desired To clear the decimal press the arrow key fur thest to the right PRGM This is the scaling factor for the count input To change press the arrow key under the digit...

Страница 17: ...clear the decimal press the arrow key furthest to the right Press the ENTER key to enter the displayed location This section sets the second counter operation Press the program key to choose GR TOT G...

Страница 18: ...d digits to change Press ENTER to enter displayed value This sets the number of significant figures to be displayed Press the arrow key un der the digit to change Press ENTER to enter displayed value...

Страница 19: ...fter CODE flashes the display will show the existing lock code To change the code press the key under each digit to be changed Press ENTER to enter displayed value see below to turn lock ON or OFF Key...

Страница 20: ...elected This is the duration 01 to 99 99 sec that relay B will remain energized If 00 00 is selected the relay will latch until reset PRE A Preset A Batch Amount The set point at which output A will d...

Страница 21: ...rompt you to choose another baud rate This will occur until a valid baud rate is entered or escape is pressed PARITY Parity is a bit of information that is inserted before the stop bit and is used to...

Страница 22: ...case The terminal addressing the unit must be capable of driving all loads in the loop The input impedance of RS422 is much higher and there should be no problem driving as many as 99 units The trans...

Страница 23: ...it to a computer with RS 422 five connections are needed These connections are Re ceive data A Receive data B Transmit data A Transmit data B and Ground The connections should be made as follows DP 9...

Страница 24: ...alues SWITCH 2 Select Count or Rate SW2 OFF down Analog output follows rate SW2 ON up Analog output follows count SWITCH 3 Select 4 20mA or 0 20mA SW3 OFF down Selects 4 20mA output range SW3 ON up Se...

Страница 25: ...auses the counter to auto reset at the preset 1 The menu flow chart and the setup steps show the setup for units with all of the available options Options not ordered will be suppressed in the program...

Страница 26: ...therwise abused ALL OTHER WARRANTIES EXPRESSED OR IMPLIED ARE EXCLUDED INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE Example MB2 A 3 1 A S...

Отзывы: