PROGRAMMING FLOWCHART

RATE

TOTAL

CLR ToT

FDEC

12345678

M

RUN MODE

CLEAR TOTAL

FACTOR

DECIMAL

FAC

100

FACTOR

0000

ent Code

ENTER CODE

If panel

lock ON

If panel

lock OFF

If  code

correct

If  code

incorrect

FAC

20poInt

FACTOR

TYPE

20poInt

lInear

lInear

selected

E

M

E

E

M

E

M

E

M

20poInt

selected

Continue On

Next Page

Fr#

#####

FREQUENCY

for POINT #

(Fr0-Fr19)

FaC#

#####

FACTOR for

POINT #

(FAC0-FAC19)

If  Fr1-FR19 = 0

# = 19

E

M

E

M

YES

   SET pnts

E

M

YES

No

SET

20PT

YES

selected

No

selected

Press the 

key to enter the programming menu.

The 

SET pnts

 prompt will only appear if 

20point 

is selected. This allows 

users to bypass the 20 point set up and keep the existing values.

Press the   key to choose YES or NO.

Press the 

key to enter the displayed selection.

Press the 

key to skip (same as selecting NO).

If the panel lock is on, you must enter the 4 digit lock code to gain access 

to the menu.

Press the   key to increment each individual digit of the code.

Press the   key to advance to the next digit.

Press the 

key to enter the displayed code.

If the code is correct, display advances to "

clr tot

", if not, display returns 

to run mode

Press the 

key  to  clear  the  totalizer  and  return  to  the  programming 

menu.

Press the 

key to skip and go to next menu item.

Press the   key to step the factor decimal to the desired location.

Press the 

key to enter the displayed decimal location.

Press the 

M key

 to skip and keep the existing location

NOTE:

  For best performance and resolution choose as many decimal places as 

possible in the K-Factor.Example: Enter a K-Factor of 1 as 1.000.

Press the   key to choose factor type (

20point 

or 

linear

).

Press the 

key to enter the displayed factor type.

Press the 

key to skip and keep the existing factor type.

Press the   key to increment each individual digit of the factor for point #.

Press the   key to advance to the next digit.

Press the 

key to enter the displayed factor.

Press the 

key to skip and keep the existing factor.

If 0 is entered, the display will advance to the next prompt (tdec).

Press the    key  to  increment  each  individual  digit  of  the  frequency  for 

point #.

Press the 

 key to advance to the next digit.

Press the 

key to enter the displayed frequency.

Press the 

key to skip and keep the existing frequency.

If 0 is entered, the display will advance to the next prompt (tdec).

NOTE:

  Frequency/factor  point  pairs  must  be  entered  in  ascending  order  of  fre-

quency

The 

FAC

 prompt will only appear if 

linear 

is selected or if the unit was 

ordered without the 20 point linearization option.

Press the   key to increment each individual digit of the factor.

Press the   key to advance to the next digit.

Press the 

key to enter the displayed factor.

Press the 

key to skip and keep the existing factor.

Содержание BAT R/T Millennium-S1

Страница 1: ...Ratemeter Totalizer with RS232 Serial Port Installation and Operating Instructions 99982 11 10 15 KESSLER ELLIS PRODUCTS 10 Industrial Way East Eatontown NJ 07724 800 631 2165 732 935 1320 Fax 732 935...

Страница 2: ......

Страница 3: ...Installation and Replacement 3 Dimensions 4 Theory of Operation 5 Wiring 5 Typical Applications 5 Definitions 6 Programming Flowchart 9 Operation 12 Error Messages 13 Analog Output Calibration 13 War...

Страница 4: ......

Страница 5: ...MOSPHERE DE C DE GROUPE AVERTIR BOUCHER LES ENTREES INUTILISEES DE CONDUIT AVEC UN BOUCHON DE CONDUIT CERTIFIE ENVIRONMENTAL OPERATING TEMPERATURE 4 F 20 C to 158 F 70 C Extended Temp 22 F 30 C to 158...

Страница 6: ...battery life by 20 IDATA STORAGE Setup Information Stored in flash memory Totalizer Stored in battery backed RAM but can be saved to flash memory by operator for recall after battery change out COMMU...

Страница 7: ...iptor BAT illuminates when the battery voltage falls below this predetermined value The low battery detector operates correctly with all power options The battery or batteries should be replaced withi...

Страница 8: ...RT M 0 BATRT M 1 E M 3 0120 DIAMETER 900 22 8 992 25 2 Mounting holes 125 Drill 2 places 438 Nylon Spacer Supplied 1 8 46 2 875 73 10 2 5 438 11 1 900 22 8 992 25 2 2 40 61 2 20 56 0 95 24 0 30 max 7...

Страница 9: ...t frequency is used to access the table A linear interpolation of adjacent point pairs is used to arrive at the K Factor at that input frequency The flow rate and total are then computed based upon th...

Страница 10: ...t is linear over its entire operating flow range Press the key to step to the desired choice Press the E key to enter the displayed factor type No yes set Pnts set 20 point This prompt allows the user...

Страница 11: ...ay r deCloC ratemeter decimal location Sets the decimal location for the ratemeter information The ratemeter deci mal is not a dummy decimal and will scale the rate display accordingly i e if the r de...

Страница 12: ...g display will result Pressing the M key will result in a display of an error mes sage E PULSE Press the E key to return to the run mode P uuidth pulse width Sets the pulse width of the pulse output S...

Страница 13: ...ep the factor decimal to the desired location Press the E key to enter the displayed decimal location Press the M key to skip and keep the existing location NOTE For best performance and resolution ch...

Страница 14: ...ress the E key to enter the displayed value Press the M key to skip and keep the existing value Press the key to increment each individual digit of the out high setting 20mA value This will only displ...

Страница 15: ...setting Press the E key to enter the displayed lock setting Press the M key to skip and keep the existing setting Press the key to increment each individual digit of the lock code Press the key to ad...

Страница 16: ...panel switch sequence or by a contact closure on the remote reset terminal to circuit common To reset the unit from the front panel the following key sequence is required Press M CLr tot will be displ...

Страница 17: ...display an arbitrary total when new battery is installed In this case reset the total to 0 and check the setup information ANALOG OUTPUT CALIBRATION CAUTION Performing the analog output calibration wi...

Страница 18: ...y 4 20 Point Linearization 10 point with S2 option D Rate per Day Hour or Minute ET Extended Temp 22 F to 158 F 30 C to 70 C CE CE Approved Version LVD EMC only CSA CSA Approved Version explosion proo...

Страница 19: ...15 Revision History 03 09 05 Original release 11 10 15 Added Specifications and Dimensions for 3NE and 3SS mounting options...

Отзывы: