* Slow input pulse rates, large delay setting and internal math 

operations may delay the update rate of information.

SPECIFICATIONS

Description

Featuring 5 digits of rate and 8 digits of total, the BAT 

R/T Millennium edition (BATRT-M) is a battery or loop 

powered indicator capable of accepting magnetic pickup, 

DC pulse and switch closure inputs from pulse produc-

ing flowmeters. The unit can be ordered with an optional 

4-20mA output.  The BATRT-M uses the 4-20mA loop to 

provide power when this output is used.

Specifications

  

DISPLAY:

Rate Display: (selectable decimal)

  5 Digits (99999), 0.35” High, Display updates once per 

second with battery power, 8X per second with DC or 

Loop power

  Rate Descriptors:  /SEC, /MIN, /HR

   

/MIN, /HR, /DAY with “D” option

  Min.  Input  Frequency:  0.01  Hz  to  10  Hz  (selectable 

delay of 0.1 to 99.9 seconds) Selectable Rate Display 

Damping

Totalizer Display:  (selectable decimal)

  8 Digits (99999999), 0.2” High

  Totalizer Descriptors:  GAL, LIT, FT3, M3,  “blank” 

    

GAL, BBL, MCF, M3,  “blank” with  

 

“D” option

Warning Displays: Low battery warning

PULSE OUTPUT:

  The  pulse  output  advances  with  the  least  significant 

digit of the totalizer or decimal multiples there of (see 

Pulse scale divider).

  Type: Isolated photomos relay

  Max. voltage (off state): 30 VDC

  Current (on state): 100mA

  Pulse  Duration:  Selectable  0.5,  0.25,  0.125,  0.0625 

seconds

  Pulse  Scale  divider  (Pulscale):  User  selectable,  ÷1, 

÷10, ÷100 or OFF

  NOTE: Select OFF for max. battery life.

ACCURACY

:

  0.01% Reading, ±1 count

  Temperature Drift: 50 ppm/°C Worst Case

SAFETY LISTINGS (Mounting Styles 3, 3NE, 3SS):

  CSA File 091109 (cert. 1120094)

  UL/C-UL File E225832

  CLASS 1, DIV 1, GROUPS B, C, D 

  Additional "enclosure only" approvals available for ATEX and 

IEC

CAUTION; 

 KEEP  COVER  TIGHT  WHILE  CIRCUITS  ARE 

ALIVE,    A  SEAL  SHALL  BE  INSTALLED  WITHIN 

450mm (18 in) OF THE ENCLOSURE WHEN USED 

IN GROUP B ATMOSPHERES AND WITHIN 1.5m (5 

ft) WHEN USED IN GROUP C ATMOSPHERE

CAUTION

;  PLUG ANY UNUSED CONDUIT ENTRIES WITH A 

CERTIFIED CONDUIT PLUG

AVERTIR

;   GARDER  LA  COUVERTURE  TENDUE  PENDANT 

QUE  CIRCUITS  SONT  VIVANTS  ,    UN  CACHET 

SERA  INSTALLE  DANS  450  mm  (18  dans)  DE 

LA  CLOTURE  QUAND  UTILISE  DANS  LES 

ATMOSPHERES DE B DE GROUPE ET DANS 1.5m 

(5 ft) QUAND UTILISE DANS L’ATMOSPHERE DE 

C DE GROUPE

AVERTIR

;  BOUCHER  LES  ENTREES  INUTILISEES  DE 

CONDUIT  AVEC  UN  BOUCHON  DE  CONDUIT 

CERTIFIE

ENVIRONMENTAL:

OPERATING TEMPERATURE

   -4°F (-20°C) to  + 158°F (70°C)

  Extended Temp:  -22°F  (-30°C) to + 158°F (70°C)

HUMIDITY

  0 - 90% Noncondensing

MOUNTING STYLES:

0

- Circuit Board- 

OEM option (consult factory)

1

- Panel Mount -  

NEMA 4X Front

2

- Wall Mount -  

NEMA 4X Enclosure

 

 (keypad mounted behind clear cover)

3

- Explosion Proof -  Class I, Division I, Groups B, C & D

 

Class II, Division I, Groups E, F & G

3ΝΕ

- Explosion Proof - White, Includes Third Conduit Entry 

Class I, Division I, Groups B, C & D

 

Class II, Division I, Groups E, F & G

3SS

- Explosion Proof - Stainless Steel 

Class I, Division I, Groups B, C & D

 

Class II, Division I, Groups E, F & G

5

- Wall Mount -  

NEMA 4X Enclosure 

 

(keypad mounted on cover)

6

- Double Ended Explosion Proof -  

 

Class I, Division I, Groups B, C & D

 

Class II, Division I, Groups E, F & G

 

(contact factory for details)

NOTE:

  Meter mounting kits available for styles 2, 3, 5 and 6

   

Consult Factory

NPUTS:

MAGNETIC PICKUP INPUT

  Frequency Range: 0 to 3500 Hz 

  Trigger Sensitivity: 10 mV p-p 

  Over Voltage Protected: ± 30 VDC

OPTO-ISOLATED DC PULSE INPUT

  High (logic 1): 4-30 VDC

  Low (logic 0): Less Than 1 VDC

  Minimum Current: .5 mA

  Hysteresis: 0.4 VDC

  Frequency Range: 0 to 5 kHz  

  Min. Pulse Width: 0.1 msec

CONTACT CLOSURE INPUT (contact closure to common)

  Internal Pullup Resistor: 100 KΩ to +3.6 VDC

  High (logic 1): Open or 4-30 VDC

  Low (logic 0): Less Than .5 VDC

  Internal Switch Debounce Filter: 0 to 40 Hz

 

NOTE

:   Sustained contact closure will shorten battery life.

RESET INPUT (contact closure to common)

  Internal Pullup Resistor: 100 KΩ to +3.6 VDC

  High (logic 1): Open or 4-30 VDC

  Low (logic 0): Less Than .5 VDC

  Minimum On : 25 msec

 

NOTE

:   Sustained contact closure will shorten battery life.

K-FACTOR

  Range: 0.001 to 99999999

  Decimal Point Locations: XXXX.XXXX to XXXXXXXX

20 Point Linearization Option (10 Point with Data Logger option)

  This feature allows the user to enter 20 different frequencies 

with 20 different corresponding K-Factors to linearize non lin-

ear signals.

ANALOG OUTPUT OPTION:

  Type: 4-20 mA follows rate display, Two wire hookup

  Accuracy: 0.025% Full Scale at 20° C

  Temperature Drift: 

   

50 ppm/°C Typical

  Reverse Polarity Protected

  Update Rate: 8 times/second

NOTE:

 The BATRT-M uses the 4-20 mA loop power as its pri-

mary power source when this option is used.  The battery 

is still required for standby battery operation.

Содержание BAT R/T Millennium-S1

Страница 1: ...Ratemeter Totalizer with RS232 Serial Port Installation and Operating Instructions 99982 11 10 15 KESSLER ELLIS PRODUCTS 10 Industrial Way East Eatontown NJ 07724 800 631 2165 732 935 1320 Fax 732 935...

Страница 2: ......

Страница 3: ...Installation and Replacement 3 Dimensions 4 Theory of Operation 5 Wiring 5 Typical Applications 5 Definitions 6 Programming Flowchart 9 Operation 12 Error Messages 13 Analog Output Calibration 13 War...

Страница 4: ......

Страница 5: ...MOSPHERE DE C DE GROUPE AVERTIR BOUCHER LES ENTREES INUTILISEES DE CONDUIT AVEC UN BOUCHON DE CONDUIT CERTIFIE ENVIRONMENTAL OPERATING TEMPERATURE 4 F 20 C to 158 F 70 C Extended Temp 22 F 30 C to 158...

Страница 6: ...battery life by 20 IDATA STORAGE Setup Information Stored in flash memory Totalizer Stored in battery backed RAM but can be saved to flash memory by operator for recall after battery change out COMMU...

Страница 7: ...iptor BAT illuminates when the battery voltage falls below this predetermined value The low battery detector operates correctly with all power options The battery or batteries should be replaced withi...

Страница 8: ...RT M 0 BATRT M 1 E M 3 0120 DIAMETER 900 22 8 992 25 2 Mounting holes 125 Drill 2 places 438 Nylon Spacer Supplied 1 8 46 2 875 73 10 2 5 438 11 1 900 22 8 992 25 2 2 40 61 2 20 56 0 95 24 0 30 max 7...

Страница 9: ...t frequency is used to access the table A linear interpolation of adjacent point pairs is used to arrive at the K Factor at that input frequency The flow rate and total are then computed based upon th...

Страница 10: ...t is linear over its entire operating flow range Press the key to step to the desired choice Press the E key to enter the displayed factor type No yes set Pnts set 20 point This prompt allows the user...

Страница 11: ...ay r deCloC ratemeter decimal location Sets the decimal location for the ratemeter information The ratemeter deci mal is not a dummy decimal and will scale the rate display accordingly i e if the r de...

Страница 12: ...g display will result Pressing the M key will result in a display of an error mes sage E PULSE Press the E key to return to the run mode P uuidth pulse width Sets the pulse width of the pulse output S...

Страница 13: ...ep the factor decimal to the desired location Press the E key to enter the displayed decimal location Press the M key to skip and keep the existing location NOTE For best performance and resolution ch...

Страница 14: ...ress the E key to enter the displayed value Press the M key to skip and keep the existing value Press the key to increment each individual digit of the out high setting 20mA value This will only displ...

Страница 15: ...setting Press the E key to enter the displayed lock setting Press the M key to skip and keep the existing setting Press the key to increment each individual digit of the lock code Press the key to ad...

Страница 16: ...panel switch sequence or by a contact closure on the remote reset terminal to circuit common To reset the unit from the front panel the following key sequence is required Press M CLr tot will be displ...

Страница 17: ...display an arbitrary total when new battery is installed In this case reset the total to 0 and check the setup information ANALOG OUTPUT CALIBRATION CAUTION Performing the analog output calibration wi...

Страница 18: ...y 4 20 Point Linearization 10 point with S2 option D Rate per Day Hour or Minute ET Extended Temp 22 F to 158 F 30 C to 70 C CE CE Approved Version LVD EMC only CSA CSA Approved Version explosion proo...

Страница 19: ...15 Revision History 03 09 05 Original release 11 10 15 Added Specifications and Dimensions for 3NE and 3SS mounting options...

Отзывы: