www.kemper-olpe.de
– 03.2021 / K410054000001-00 – 23/88
1. Remove sign cap (3).
2. Insert hexagonal span-
ner (6mm width across
flats) into the authority
top part (4) and close
valve by turning it to the
right.
3. Now, the temperature,
pre-set at the factory,
can be modified by
maximum half a turn to
the right. 10 notch steps
correspond to 2 K.
4. Check the correct posi-
tion of the regulating
piston (end position!)
by turning the shut-off
spindle (5) to the left.
Modification of
Factory Setting
3
Note!
After this, the valve
has again to be fully
opened (left turn to
end position).
Note!
Do not over-tighten
the end position
buffers!