©
www.kemper-olpe.de
– 03.2021 / K410054000001-00 – 17/88
Technical data
KEMPER Figures
130, 131, 540 02, 544 02
134, 136, 540 62
Adjustable
regulating range
56°C - 58°C
62°C - 64°C
Factory setting
58°C
64°C
Temperature
range for Thermal
disinfection
≥ 70°C
≥ 70°C
Max. permissible
operating temper-
ature
90°C
90°C
K
v
values
max. 0,4 m³/h | min. 0,05 m³/h | k
vTD
0,1 m³/h
Nominal pressure
PN 16
PN 16
Nominal sizes
DN 15
DN 15
Design
concealed or surface
installation
concealed or surfa-
ce installation
Noise protection
The pressure difference
Δ
p across the regulat-
ing valve should always be above ≤ 400 mbar.
Technical data
1