Manual KHS Mini System Control MASTER
14
6.2.2.9
Connection of water sensor (Figure 620 00)
Note:
It is possible to link up to 25 water
sensors in parallel in the detection
circuit
.
Max. cable length water sensor:
< 50m
with standard cable
Max. cable length water sensor:
> 50m
to
500m
as shielded cable,
2x 0.75 mm², (e.g. UL-LIYCY)
W = white = 22
BN = brown = 23
Ill. 6.15:
Exemplary diagram of the water sensor connection
6.2.2.10
Connection of floating alarm relay
Monitoring example: Errors and mains
voltage failures are reported with
external voltage to the warning lamp, the
warning horn or to the BMS.
Ill. 6.16: Exemplary diagram of the alarm relay
Warning light
Alarm horn
e.g input BMS or
alarm relay
External voltage max.
230V, 2A or 24V input