Manual KHS Mini System Control MASTER
6
CAN bus
A
CAN bus
A
CAN bus
B
CAN bus
A
Example 2: Incorrect layout
Ill. 5.2 View of an impermissible layout variant, KHS Mini System Control -Master-
5.2
Terminal resistance
Variant 1
Note:
The
120
Ω
terminal
resistance must be installed
only in the last control
component (-SLAVE-) of a
CAN bus cable line. The
-MASTER- control does not
require
a
terminal
resistance.
Variant 2
Ill. 5.3 Illustration of a CAN bus line with terminal resistor
5.3 Connection of terminal resistor
Attention:
All
KHS
Mini
controls
-SLAVE- are supplied with a
120 Ω terminal resistor.
For non-terminal -SLAVE-
controls, the resistor must be
removed!
120
Ω
Note:
Incorrect layout
Ill. 5.4 Illustration of the terminal resistor
connection