Installation 

CNA-Series Tankless Heater

Keltech • 

215-1814 Rev. C; ECN 150010 

7/13/2015

Electric Installation

3

B

Using a hole punch, cut a hole the 
proper size for conduit connection; 
large enough for the wire size for each 
heater . The connectors need to be rated 
NEMA4/4X to ensure proper sealing of 
the enclosure . .

A

Open enclosure door .

C

Run wires through the appropriate size 
conduit .

D

Connect wires to the system terminal 
block or fused disconnect inside the 
enclosure .  

E

Connect the ground wire to the stud 
provided with the “Ground” label beneath it .  

NOTICE!  Any option that requires field wiring 

must be done with 600V cable per 
the schematic that was shipped with 
the heater.

NOTICE!  Use a 4-core cable or multi-stranded 

machine tool wire from an approved 
isolating 3-pole switch or circuit 
breaker.

NOTICE!  Make sure the electrical cable is the 

correct size to carry 100% of the full 
load current. See table for proper 
wire sizes.

WARNING All Keltech heaters must be fused in accordance with National Electric Code (NEC) for the 

full load amperage listed on the nameplate rating for each heater.

WARNING  Failure to properly ground the unit(s) per the National Electric Code could result in injury or 

death.

CNA & CNAR ELECTRICAL SPECIFICATIONS FOR HEATER**

Model

Voltage

Amps

kWatts

Min Wire 

Size

CNA-363/600D

600

35

36

8 AWG*

CNA-543/600D

600

52

54

6 AWG*

CNA-633/600D

600

61

63

4 AWG*

CNA-723/600D

600

69

72

4 AWG*

CNA-1083/600D

600

104

108

2 AWG*

CNA-1263/600D

600

121

126

1 AWG*

CNA-1443/600D

600

139

144

1/0 AWG*

CNA-363/480D

480

43

36

6 AWG*

CNA-543/480D

480

65

54

4 AWG*

CNA-633/480D

480

76

63

4 AWG*

CNA-723/480D

480

87

72

3 AWG*

CNA-1083/480D

480

130

108

1 AWG*

CNA-1263/480D

480

152

126

1/0 AWG*

CNA-1443/480D

480

174

144

2/0 AWG*

CNA-363/415D

415

38

27

8 AWG*

CNA-543/415D

415

56

40

6 AWG*

CNA-633/415D

415

65

47

4 AWG*

CNA-723/415D

415

75

54

4 AWG*

CNA-1083/415D

415

113

81

2 AWG*

CNA-1263/415D

415

131

94

1 AWG*

CNA-1443/415D

415

150

108

1/0 AWG*

CNA-363/400D

400

36

25

8 AWG*

CNA-543/400D

400

53

37

6 AWG*

CNA-633/400D

400

64

44

4 AWG*

CNA-723/400D

400

72

50

4 AWG*

CNA-1083/400D

400

108

75

2 AWG*

CNA-1263/400D

400

126

87

1 AWG*

CNA-1443/400D

400

144

100

1/0 AWG*

CNA-363/380D

380

35

23

8 AWG*

CNA-543/380D

380

50

33

6 AWG*

CNA-633/380D

380

59

39

6 AWG*

CNA-723/380D

380

68

45

4 AWG*

CNA-1083/380D

380

103

68

2 AWG*

CNA-1263/380D

380

120

79

1 AWG*

CNA-1443/380D

380

137

90

1/0 AWG*

* Based on the NEC Table 310 .15 for 75°C insulated wire @ 30°C Ambient

** CNAR (reverse models) electrical specifications are same as CNA heater 
models .

Содержание CNA-36

Страница 1: ...A 126 CNA 144 CNAR 108 CNAR 126 CNAR 144 Voltage options for models 600V 3 phase 480V 3 phase 415V 3 phase 400V 3 phase 380V 3 phase Table of Contents Pre Installation Information 2 3 Storage Instruct...

Страница 2: ...d this system may result in death or serious injury Make sure that all water supply lines have been flushed and then completely turned off before beginning installation Debris in supply lines can caus...

Страница 3: ...in the most demanding applications Application Specific Requirements The CNA Series can be used in many different applications that require custom tuning for specific applications to maximize perform...

Страница 4: ...eaters with ENHT freeze protection option If the heater is stored where the temperature could fall below 45 F 7 C the heater must be powered immediately after hydro testing to insure internal freeze p...

Страница 5: ...les 30 762mm 12 305mm 2 51mm 4 102mm 8 204mm 6 7 8 175mm 16 1 4 413mm 3 7 8 99mm 3 4 x 7 16 Slot 6 Places If heater is installed where freezing can occur specify Keltech s ENHT Freeze Protection optio...

Страница 6: ...umbing loop then an automatic air vent valve must be added at the highest point in the system or at any drop to eliminate trapped air Components Needed 4 Union 1 1 4 Shutoff Valve Pressure and Tempera...

Страница 7: ...nal Electric Code could result in injury or death CNA CNAR ELECTRICAL SPECIFICATIONS FOR HEATER Model Voltage Amps kWatts Min Wire Size CNA 363 600D 600 35 36 8 AWG CNA 543 600D 600 52 54 6 AWG CNA 63...

Страница 8: ...e relief valve on outlet if required by local or national plumbing codes If the hot water process is not at the highest point in the plumbing loop then an automatic air vent valve must be added at the...

Страница 9: ...area where freezing temperatures are possible an ENHT Freeze Protection Option is strongly recommended and the heater must be powered at all times to be Freeze Protected If continuous power is not po...

Страница 10: ...temperature Infinity Key Back to Home page Advance Key Advances through parameter prompts Auto Man Off C r71 Turns Control Loop On Manual Off XX X h Pr1 Heater Power no AUt1 Autotune Contact Factory C...

Страница 11: ...ecessary Located on the panel are one 36 63kW or two 72kW 144kW green ready lights When illuminated the safety circuit is engaged and ready for use Heater will not energize heating elements if the inl...

Страница 12: ...ng process are compatible with the heater specifications 5 Verify there is no additional supply of cold water entering the line downstream of the heater Temperature Rise GPM F Models 480 600V Total kW...

Страница 13: ...ntain power at all times or to connect the contacts provided on ENHT heaters correctly to the BMS may result in damage to the heater and void the warranty Please utilize the temperature sensor contact...

Страница 14: ...ing the manual reset safeties to trip Reset bimetal manual safeties and lower heat trace temperature to below 175 F All heaters require filtration of 150 microns or smaller to ensure proper operation...

Страница 15: ...ce circuit breakers or fuses Check the safety interlock door switch to make sure that lack of power is not due to misadjustment or open enclosure door Check system temperature limit control to make su...

Страница 16: ...ezel Bank 1 on the FLCB Bank 3 4 on the front bezel Bank 2 on the FLCB If the light is off and there is power on Check if water temperature is greater than 175 F Decrease water temperatures and restar...

Страница 17: ...osure Purge gas compressed air inlet fitting here EXP2CFPM Installation Notes 1 Any tubing conduit or fittings connected to the Pressurized Enclosure PE must conform to local codes for flammability ra...

Страница 18: ...sure and the protective gas supply The alarm actuator shall be mechanical pneumatic or electrical Electrical alarms and electrical alarm actuators shall be approved for the location in which they are...

Страница 19: ...ay be fitted between the Expo Technologies system and the alarm switch WARNING Never turn on the power without purging first unless you have proved the interior of the PE is gas free and checked that...

Страница 20: ...arms function correctly Check the Relief Valve and any other Spark Arrestors Remove any debris or corrosion or replace the Spark Arrestor Check the condition of the air supply filter element Clean or...

Отзывы: