Keltech CNA-36 Скачать руководство пользователя страница 14

14

CNA-Series Tankless Heater

 Installation

7/13/2015 

Keltech • 

215-1814 Rev. C; ECN 150010

Maintenance 

Preventative maintenance is important for optimal performance of the heater . To ensure the heater works properly, 
always keep the inside of the enclosure dry . Moisture inside an enclosure increases the humidity, which condenses 
on cooler surfaces . This can cause electrical problems and reduce the efficiency of enclosure insulation . To prevent 
problems perform the following:
•  Verify the interior of the enclosure is dry .

•  Verify there are no leaks in seals of enclosure and that in high humidity environments all enclosure egresses are 

properly sealed .

•  Ensure plugs are in place on back side of enclosure .

•  Check seals monthly during temperatures above 32°F (0°C) and weekly during temperatures below 32°F(0°C) . 

Check internal freeze protection system(ENHT, ENHT30)  prior to first seasonal freeze for proper performance . The 
external heater and internal thermostat are factory set at 55°F(13°C) .  Check weekly during temperatures below 
32°F (0°C) . See Information in Product Options section for additional information on freeze protection . 

•  Bimetal manual reset safeties mounted to the heat exchangers may trip at temperatures below 32°F on heaters 

equipped with ENHT or ENHT30 . The bimetal manual resets are set to trip at 175°F(79°C) . Heat trace installed on 
piping can heat water to temperatures above 100°F(38°C), causing the manual reset safeties to trip . Reset bimetal 
manual safeties and lower heat trace temperature to below 175°F .

•  All heaters require filtration of 150 microns or smaller to ensure proper operation . Y-strainers or additional filtration 

should be verified and cleaned at least every 6 months or more often in areas where hard water sediment is 
present in the water . 
 
To clean the Y-Strainer:

1 .  Turn the power off at the circuit breaker panel . 
2 .  Shut off the installer supplied cold water isolation valve to the heater .
3 .  Relieve pressure in the plumbing lines .
4 .  Position a bucket under the cold water inlet to catch any water that may still be in the pipe .
5 .  Loosen the plumbing connection on the Y-strainer to get to the screen .
6 .  Remove screen and clean out debris . Use a wire brush to clean smaller particles from the screen .
7 .  Once the screen is clean, put it back into the Y-strainer housing and secure the plumbing connection .
8 .  Before switching the power back on, bleed the air out of the lines by turning heater water supply back on and 

the plumbing fixture or process farthest from the heater .

9 .  With the air purged, turn on all circuit breakers supplying the water heater . 

•  At the same time the Y-strainer or additional filtration is cleaned, it is a good practice to also check all valves 

connected to the system . With no water flow through the heater, work both the inlet ball valves and the outlet gate 
valves open and shut to break up any calcium deposits that may have formed from the valve being open for an 
extended period of time . Power to the heater does not need to be turned off to do this .

Содержание CNA-36

Страница 1: ...A 126 CNA 144 CNAR 108 CNAR 126 CNAR 144 Voltage options for models 600V 3 phase 480V 3 phase 415V 3 phase 400V 3 phase 380V 3 phase Table of Contents Pre Installation Information 2 3 Storage Instruct...

Страница 2: ...d this system may result in death or serious injury Make sure that all water supply lines have been flushed and then completely turned off before beginning installation Debris in supply lines can caus...

Страница 3: ...in the most demanding applications Application Specific Requirements The CNA Series can be used in many different applications that require custom tuning for specific applications to maximize perform...

Страница 4: ...eaters with ENHT freeze protection option If the heater is stored where the temperature could fall below 45 F 7 C the heater must be powered immediately after hydro testing to insure internal freeze p...

Страница 5: ...les 30 762mm 12 305mm 2 51mm 4 102mm 8 204mm 6 7 8 175mm 16 1 4 413mm 3 7 8 99mm 3 4 x 7 16 Slot 6 Places If heater is installed where freezing can occur specify Keltech s ENHT Freeze Protection optio...

Страница 6: ...umbing loop then an automatic air vent valve must be added at the highest point in the system or at any drop to eliminate trapped air Components Needed 4 Union 1 1 4 Shutoff Valve Pressure and Tempera...

Страница 7: ...nal Electric Code could result in injury or death CNA CNAR ELECTRICAL SPECIFICATIONS FOR HEATER Model Voltage Amps kWatts Min Wire Size CNA 363 600D 600 35 36 8 AWG CNA 543 600D 600 52 54 6 AWG CNA 63...

Страница 8: ...e relief valve on outlet if required by local or national plumbing codes If the hot water process is not at the highest point in the plumbing loop then an automatic air vent valve must be added at the...

Страница 9: ...area where freezing temperatures are possible an ENHT Freeze Protection Option is strongly recommended and the heater must be powered at all times to be Freeze Protected If continuous power is not po...

Страница 10: ...temperature Infinity Key Back to Home page Advance Key Advances through parameter prompts Auto Man Off C r71 Turns Control Loop On Manual Off XX X h Pr1 Heater Power no AUt1 Autotune Contact Factory C...

Страница 11: ...ecessary Located on the panel are one 36 63kW or two 72kW 144kW green ready lights When illuminated the safety circuit is engaged and ready for use Heater will not energize heating elements if the inl...

Страница 12: ...ng process are compatible with the heater specifications 5 Verify there is no additional supply of cold water entering the line downstream of the heater Temperature Rise GPM F Models 480 600V Total kW...

Страница 13: ...ntain power at all times or to connect the contacts provided on ENHT heaters correctly to the BMS may result in damage to the heater and void the warranty Please utilize the temperature sensor contact...

Страница 14: ...ing the manual reset safeties to trip Reset bimetal manual safeties and lower heat trace temperature to below 175 F All heaters require filtration of 150 microns or smaller to ensure proper operation...

Страница 15: ...ce circuit breakers or fuses Check the safety interlock door switch to make sure that lack of power is not due to misadjustment or open enclosure door Check system temperature limit control to make su...

Страница 16: ...ezel Bank 1 on the FLCB Bank 3 4 on the front bezel Bank 2 on the FLCB If the light is off and there is power on Check if water temperature is greater than 175 F Decrease water temperatures and restar...

Страница 17: ...osure Purge gas compressed air inlet fitting here EXP2CFPM Installation Notes 1 Any tubing conduit or fittings connected to the Pressurized Enclosure PE must conform to local codes for flammability ra...

Страница 18: ...sure and the protective gas supply The alarm actuator shall be mechanical pneumatic or electrical Electrical alarms and electrical alarm actuators shall be approved for the location in which they are...

Страница 19: ...ay be fitted between the Expo Technologies system and the alarm switch WARNING Never turn on the power without purging first unless you have proved the interior of the PE is gas free and checked that...

Страница 20: ...arms function correctly Check the Relief Valve and any other Spark Arrestors Remove any debris or corrosion or replace the Spark Arrestor Check the condition of the air supply filter element Clean or...

Отзывы: