Installation 

CNA-Series Tankless Heater

Keltech • 

215-1814 Rev. C; ECN 150010 

7/13/2015

IS Installation continued…

All quarter turn latches in the door of the PE must be fully latched for proper operation . Power to the PE must be 
turned off before opening the enclosure .

WARNING This Pressurized Enclosure shall not be opened unless the area is known to be free of 

flammable materials or unless all devices within have been de-energized.

Power shall not be restored after the enclosure has been opened until the enclosure has been purged for allotted 
time (See table below) . Time begins when pressure indicator turns green after the door of the enclosure has been 
closed and fully latched . 

WARNING Ignition of potentially explosive gas/air mixtures may result if power is turned on before the 

allotted purge time!

Expo Technologies CF systems have a Minimum Pressure Sensor set to a pressure of at lease 0 .1" WC (0 .25bars) . When 
the PE pressure is above this set point the sensor produces a positive Pressurized signal . This is displayed on the Red/
Green indicator located on the Purge System . This signal can be used to operate an electrical contact for a remote Alarm . 
This signal may be supplied to the pressure operated switch suitable for Intrinsically Safe circuit in accordance . When the 
enclosure pressure falls below the set point of the sensor, the Pressurized signal is removed, and the Alarm conditions 
occurs . This Alarm must be located where it can be readily observed according to NFPA496 requirements . 

No valves may 

be fitted between the Expo Technologies system and the alarm switch.

WARNING  Never turn on the power without purging first, unless you have proved the interior of the PE is gas 

free and checked that the “Pressurized” indicator is green!

Commissioning Test

Commissioning Continuous Flow Keltech Option EXP2CFPM System:

1 .  Open the air or gas supply shutoff valve .
2 .  Adjust the Flow Control Valve (FCV) so that the enclosure pressure rises to the point where the "Pressurized" 

indicator turns green .

3 .  Lower the PE pressure until the Pressurized indicator turns Red . 
4 .  Open the FCV again and set the PE pressure to a level somewhere between the Minimum Pressure 

Sensorset point and the RLV opening pressures . This working pressure is not critical . Enough pressure to keep 
the“Pressurized” indicator Green is sufficient .

5 .  On EXP2CFPM Purge System the timing function if performed by the user . The user must ensure that the time 

delay between the indicator turning Yellow and the application of power to the PE is not less than the minimum 
time required to purge the PE as shown in the table below . 

Normal Operation: 

Turn the air supply valve ON to start or OFF to stop the system . The user must close the Power 

Switch only after the enclosure has been pressurized and purged sufficiently to ensure that the interior of the enclosure 
is gas free . It is the operator’s responsibility to shut off the power as soon as possible after a pressure failure .

PURGE TIME CHART - EXP2CFPM Option 

for use with EXPO Mini Z Purge 1ZCF/pm/IS

Model/Enclosure 

Group Size

Cubic 

Feet

Volume 

Exchanges 

X 4

Orifice 

Size

Orifice 

No .

Purge 

Time 

(Minutes)

CNA-36-54

10

40

0 .9

#2

44

CNA-63

12 .5

50

0 .9

#2

55

CNA-72-108

10

40

0 .9

#2

44

CNA-126-144

12 .5

50

0 .9

#2

55

Содержание CNA-36

Страница 1: ...A 126 CNA 144 CNAR 108 CNAR 126 CNAR 144 Voltage options for models 600V 3 phase 480V 3 phase 415V 3 phase 400V 3 phase 380V 3 phase Table of Contents Pre Installation Information 2 3 Storage Instruct...

Страница 2: ...d this system may result in death or serious injury Make sure that all water supply lines have been flushed and then completely turned off before beginning installation Debris in supply lines can caus...

Страница 3: ...in the most demanding applications Application Specific Requirements The CNA Series can be used in many different applications that require custom tuning for specific applications to maximize perform...

Страница 4: ...eaters with ENHT freeze protection option If the heater is stored where the temperature could fall below 45 F 7 C the heater must be powered immediately after hydro testing to insure internal freeze p...

Страница 5: ...les 30 762mm 12 305mm 2 51mm 4 102mm 8 204mm 6 7 8 175mm 16 1 4 413mm 3 7 8 99mm 3 4 x 7 16 Slot 6 Places If heater is installed where freezing can occur specify Keltech s ENHT Freeze Protection optio...

Страница 6: ...umbing loop then an automatic air vent valve must be added at the highest point in the system or at any drop to eliminate trapped air Components Needed 4 Union 1 1 4 Shutoff Valve Pressure and Tempera...

Страница 7: ...nal Electric Code could result in injury or death CNA CNAR ELECTRICAL SPECIFICATIONS FOR HEATER Model Voltage Amps kWatts Min Wire Size CNA 363 600D 600 35 36 8 AWG CNA 543 600D 600 52 54 6 AWG CNA 63...

Страница 8: ...e relief valve on outlet if required by local or national plumbing codes If the hot water process is not at the highest point in the plumbing loop then an automatic air vent valve must be added at the...

Страница 9: ...area where freezing temperatures are possible an ENHT Freeze Protection Option is strongly recommended and the heater must be powered at all times to be Freeze Protected If continuous power is not po...

Страница 10: ...temperature Infinity Key Back to Home page Advance Key Advances through parameter prompts Auto Man Off C r71 Turns Control Loop On Manual Off XX X h Pr1 Heater Power no AUt1 Autotune Contact Factory C...

Страница 11: ...ecessary Located on the panel are one 36 63kW or two 72kW 144kW green ready lights When illuminated the safety circuit is engaged and ready for use Heater will not energize heating elements if the inl...

Страница 12: ...ng process are compatible with the heater specifications 5 Verify there is no additional supply of cold water entering the line downstream of the heater Temperature Rise GPM F Models 480 600V Total kW...

Страница 13: ...ntain power at all times or to connect the contacts provided on ENHT heaters correctly to the BMS may result in damage to the heater and void the warranty Please utilize the temperature sensor contact...

Страница 14: ...ing the manual reset safeties to trip Reset bimetal manual safeties and lower heat trace temperature to below 175 F All heaters require filtration of 150 microns or smaller to ensure proper operation...

Страница 15: ...ce circuit breakers or fuses Check the safety interlock door switch to make sure that lack of power is not due to misadjustment or open enclosure door Check system temperature limit control to make su...

Страница 16: ...ezel Bank 1 on the FLCB Bank 3 4 on the front bezel Bank 2 on the FLCB If the light is off and there is power on Check if water temperature is greater than 175 F Decrease water temperatures and restar...

Страница 17: ...osure Purge gas compressed air inlet fitting here EXP2CFPM Installation Notes 1 Any tubing conduit or fittings connected to the Pressurized Enclosure PE must conform to local codes for flammability ra...

Страница 18: ...sure and the protective gas supply The alarm actuator shall be mechanical pneumatic or electrical Electrical alarms and electrical alarm actuators shall be approved for the location in which they are...

Страница 19: ...ay be fitted between the Expo Technologies system and the alarm switch WARNING Never turn on the power without purging first unless you have proved the interior of the PE is gas free and checked that...

Страница 20: ...arms function correctly Check the Relief Valve and any other Spark Arrestors Remove any debris or corrosion or replace the Spark Arrestor Check the condition of the air supply filter element Clean or...

Отзывы: