Installation 

CNA-Series Tankless Heater

Keltech • 

215-1814 Rev. C; ECN 150010 

7/13/2015

Special Installation and Operating Instructions

Tankless Water Heaters With Optional Class I Division 2 Purge EXP2CFPM Option

General Information

All Keltech Tankless Water Heaters with a model number suffix of – EXP2CFPM have been fitted with a Z purge 
system to pressurize the enclosure suitable for use in Class I Division 2 Hazardous Locations .
A Continuous Flow (Model CF) Mini-Z Pressurizing System has been fitted to the inside of the enclosure .

Outlet

18" 

(458mm)

Max

Explosion proof 

sealing fitting 

supplied by others

Purge System 

Relief Valve

Conduit Hub 

Class 1 Div . 2 

supplied by others

Inlet

1

1

2

3

4

5

6

3

5

6

Suggested region for power 
entrance at right/bottom of 
enclosure . Entrance hole and 
components to be provided by 
installer .
All plumbing fittings are 1-1/4" NPT 
female threaded .
Purge Control Panel 
Class 1 Division 2
All installation egress from 
panel must be sealed (electrical 
conduit) for proper explosion proof 
installation .
Spark arrestor with calibration 
orifice is located in the bottom of the 
enclosure .
Purge gas/compressed air inlet 
fitting here .

EXP2CFPM Installation Notes

1 .  Any tubing, conduit or fittings connected to the Pressurized Enclosure (PE) must conform to local codes for 

flammability ratings .

2 .  All egress into PE must be plugged and properly sealed to minimize leakage of purge air . Use hazardous 

location sealing fittings suitable for Class I locations within 18" of enclosure . 

3 .  The EXP2CFPM purge system option is a continuous flow purge system mounted inside the cabinet enclosure 

and calibrated to flow at 0 .9 SCFM . To minimize waste, plug and seal all openings and conduit .

4 .  The system is designed for use primarily with compressed air . The source of the compressed air must be 

from a non-classified area (see Purge Gas Supply Notes) . Purge air must be clean, dry and free of flammable 
gases . When inert compressed gases are used (Nitrogen, for example) the installer and facility manager must 
take suitable precautions on-site so that buildup of the inert gas does not present a health hazard . Where risk 
of asphyxiation exists, a warning label must be fitted to the Pressurized Enclosure (PE) .

5 .  Adjustment of Purge System is not necessary . System is fully calibrated .
6 .  Connect to Purge System where indicated above . Connection port is 1/4" NPT female . Supply pressure must be 

regulated to 60–115 PSI .

Содержание CNA-36

Страница 1: ...A 126 CNA 144 CNAR 108 CNAR 126 CNAR 144 Voltage options for models 600V 3 phase 480V 3 phase 415V 3 phase 400V 3 phase 380V 3 phase Table of Contents Pre Installation Information 2 3 Storage Instruct...

Страница 2: ...d this system may result in death or serious injury Make sure that all water supply lines have been flushed and then completely turned off before beginning installation Debris in supply lines can caus...

Страница 3: ...in the most demanding applications Application Specific Requirements The CNA Series can be used in many different applications that require custom tuning for specific applications to maximize perform...

Страница 4: ...eaters with ENHT freeze protection option If the heater is stored where the temperature could fall below 45 F 7 C the heater must be powered immediately after hydro testing to insure internal freeze p...

Страница 5: ...les 30 762mm 12 305mm 2 51mm 4 102mm 8 204mm 6 7 8 175mm 16 1 4 413mm 3 7 8 99mm 3 4 x 7 16 Slot 6 Places If heater is installed where freezing can occur specify Keltech s ENHT Freeze Protection optio...

Страница 6: ...umbing loop then an automatic air vent valve must be added at the highest point in the system or at any drop to eliminate trapped air Components Needed 4 Union 1 1 4 Shutoff Valve Pressure and Tempera...

Страница 7: ...nal Electric Code could result in injury or death CNA CNAR ELECTRICAL SPECIFICATIONS FOR HEATER Model Voltage Amps kWatts Min Wire Size CNA 363 600D 600 35 36 8 AWG CNA 543 600D 600 52 54 6 AWG CNA 63...

Страница 8: ...e relief valve on outlet if required by local or national plumbing codes If the hot water process is not at the highest point in the plumbing loop then an automatic air vent valve must be added at the...

Страница 9: ...area where freezing temperatures are possible an ENHT Freeze Protection Option is strongly recommended and the heater must be powered at all times to be Freeze Protected If continuous power is not po...

Страница 10: ...temperature Infinity Key Back to Home page Advance Key Advances through parameter prompts Auto Man Off C r71 Turns Control Loop On Manual Off XX X h Pr1 Heater Power no AUt1 Autotune Contact Factory C...

Страница 11: ...ecessary Located on the panel are one 36 63kW or two 72kW 144kW green ready lights When illuminated the safety circuit is engaged and ready for use Heater will not energize heating elements if the inl...

Страница 12: ...ng process are compatible with the heater specifications 5 Verify there is no additional supply of cold water entering the line downstream of the heater Temperature Rise GPM F Models 480 600V Total kW...

Страница 13: ...ntain power at all times or to connect the contacts provided on ENHT heaters correctly to the BMS may result in damage to the heater and void the warranty Please utilize the temperature sensor contact...

Страница 14: ...ing the manual reset safeties to trip Reset bimetal manual safeties and lower heat trace temperature to below 175 F All heaters require filtration of 150 microns or smaller to ensure proper operation...

Страница 15: ...ce circuit breakers or fuses Check the safety interlock door switch to make sure that lack of power is not due to misadjustment or open enclosure door Check system temperature limit control to make su...

Страница 16: ...ezel Bank 1 on the FLCB Bank 3 4 on the front bezel Bank 2 on the FLCB If the light is off and there is power on Check if water temperature is greater than 175 F Decrease water temperatures and restar...

Страница 17: ...osure Purge gas compressed air inlet fitting here EXP2CFPM Installation Notes 1 Any tubing conduit or fittings connected to the Pressurized Enclosure PE must conform to local codes for flammability ra...

Страница 18: ...sure and the protective gas supply The alarm actuator shall be mechanical pneumatic or electrical Electrical alarms and electrical alarm actuators shall be approved for the location in which they are...

Страница 19: ...ay be fitted between the Expo Technologies system and the alarm switch WARNING Never turn on the power without purging first unless you have proved the interior of the PE is gas free and checked that...

Страница 20: ...arms function correctly Check the Relief Valve and any other Spark Arrestors Remove any debris or corrosion or replace the Spark Arrestor Check the condition of the air supply filter element Clean or...

Отзывы: