K-O2 Oxygen Sensor 

5/20/2022 

Kele, Inc. • 3300 Brother Blvd. • Memphis, TN  38133 

Page 7 

 

www.kele.com

 

 

Dip switch 
Setting 

 

OXYGEN % 

 

Warn  Alarm 

 

19.8 

19.5  

 

20.0 

19.5 

 

20.3 

20.0 

 

20.5 

20.0 

Table 8

:  Concentration Threshold 

Settings

Mode 

Front Cover LED 

Analog Output 

Relays Actuated 

Comment 

Normal 

Steady Green, 

Yellow or Red 

4 – 20 mA 

Depends on 

concentration 

During normal operation 

Standby  Various 

20 mA 

NONE 

During start-up interval or any time during 

calibration 

EOL 

warning 

Slow Blinking 

Yellow 

4 – 20 mA 

Depends on 

concentration 

Sensor nearing the end of its rated service 

life.   

Relays and analog output function normally. 

Sensor 

Expired  Slow Blinking Red 

4 mA 

Warning / 

Ventilation 

After calibration of expired sensor. 

Sensor is no longer operational.   

Table 9

:  K-O2 Operating Modes

 

4.2  W

ARNING 

/V

ENTILATION AND 

A

LARM 

C

ONDITIONS

 

Two, 10 Amp, 120/277 VAC rated, dry-contact, SPDT relays activate during 
warning/ventilation and alarm conditions: refer to 

Section 3.2

 

for wiring 

information.  

When the concentration of

 

oxygen falls below its configured 

warning/ventilation threshold, the 

WARNING/VENTILATION 

relay output is 

activated.  When the concentration falls below the alarm threshold, the 
controller’s

 

ALARM

 

relay is also activated.  When the oxygen concentration 

rises above the alarm threshold, the 

ALARM

 

relay is deactivated; when it rises 

above the ventilation threshold the 

WARNING

/

VENTILATION

 relay is also 

deactivated. 

4.3  S

ETTING 

V

ENTILATION AND 

A

LARM 

T

HRESHOLDS

 

The four, factory-preset pairs of ventilation and alarm levels are shown in 
Table 8.  Each setting determines both the controller’s warning/ventilation 
and alarm thresholds.   

The active threshold values are selected by setting the two DIP switches on 
the main board (see Figure 8) as shown in the first column of Table 8 for the 
desired setting. 

4.4  C

ONCENTRATION 

R

EPORTING

 

In normal mode, oxygen concentration readings from the sensor are 
reported by the controller’s powered 4 – 20mA current loop output.  The 
output connector location is shown in 

Figure 6

.  Output scaling is as shown 

in Table 5.   

 

O

2

 

Federal OSHA Personal Exposure Limit (PEL) . 

19.5 % 

 

Figure 8  

DIP Switch Locations

 

Содержание K-O2

Страница 1: ...mphis TN 38133 Revision 5 20 2022 www kele com 90 0007 00A K O2 xx Oxygen Sensor Transmitter and Two Stage Alarm Controller User s Manual K O2 H5 5 year sensor K O2 H10 10 year sensor K O2 S5 5 year s...

Страница 2: ...ional Description 5 4 1 Special Modes 6 4 2 Warning Ventilation and Alarm Conditions 7 4 3 Setting Ventilation and Alarm Thresholds 7 4 4 Concentration Reporting 7 5 Sensor Calibration 7 5 1 Calibrati...

Страница 3: ...sor life K O2 H5 Lockable hinged enclosure with 10 year sensor life K O2 H10 Table 1 K O2 family Part numbers All K O2 xx models are shipped with either 5 year life K O2 x5 or 10 year life K O2 x10 fa...

Страница 4: ...ply separate transformer not required Power Consumption 5W Control Relays 2 separate SPDT line voltage capable relays for warning ventilation and alarm outputs UL rated 10 Amps max at 120 277 VAC or 3...

Страница 5: ...water entry DO NOT USE THE VENT HOLES FOR WIRE ENTRY 1 This unit is designed to mount to a rigid vibration free surface near the middle of the area to be monitored about 5 feet above the floor 2 It s...

Страница 6: ...of the terminal and returns to the terminal The oxygen sensor output is provided at the terminal highlighted in Figure 3 Analog output connection has polarity as labeled on the controller silkscreen...

Страница 7: ...to the COM location of screw terminal 5 Plug the relay output screw terminal back into the correct location on controller board 3 3 POWER CONNECTION The K O2 has a fully isolated unpolarized power inp...

Страница 8: ...a second contact closure is operated typically to trigger an alarm The gas sensor is a calibrated module that can be replaced with minimal effort when it reaches end of life EOL while leaving the main...

Страница 9: ...ormation When the concentration of oxygen falls below its configured warning ventilation threshold the WARNING VENTILATION relay output is activated When the concentration falls below the alarm thresh...

Страница 10: ...adequate and requires no calibration gas All that s required is the certainty of fresh air around the sensor For accuracy at lower oxygen percentages a zero calibration before the span calibration is...

Страница 11: ...rictor fitted to the narrow end of the cal cap at a pressure of 10 psi 5 2 CALIBRATION GAS CONNECTION A schematic of the calibration gas tubing connection between the regulator and the calibration cap...

Страница 12: ...tion gas has been removed the calibration has been applied and the unit is in standby for two minutes while the sensor re equilibrates to the ambient atmosphere before normal operation resumes The cal...

Страница 13: ...turns to steady GREEN OR 3B If NOT successful blinking RED The most likely causes of span gas sampling failure are Insufficient gas flow or leaks around the calibration adapter not completely immersin...

Страница 14: ...n in To replace a sensor module with a new factory calibrated one follow the steps below 1 Open the controller s front cover 2 Unplug the controllers power connector refer to Figure 6 3 Unplug the sen...

Страница 15: ...patible with those Products Unless KELE agrees otherwise to obtain service under this warranty Buyer must pack any nonconforming Product carefully and ship it postpaid or freight prepaid to Kele Inc a...

Страница 16: ...tect common failures If a failure is detected the front cover status LED will blink slowly RED the warning relay will be activated and the concentration reporting analog output will stay at 4 mA until...

Отзывы: